Plan Review Notes
Plan Review Notes For Permit 01101533
Permit Number 01101533
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-30 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PLANS SHOW A
 NEW 100A SUB PANEL, BUT EXISTING MAIN
 PANEL DOES NOT LIST ON SCHEDULE??
  
 2)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED???215-5
 CONTINUOUS LOADS AT 125%.
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN EXIST AND
 NEW PANEL.250-122
  
 4)NOTE: PLANS NEED TO SHOW ALL BRANCH
 CIRCUITING AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
  
 5)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW EQUIPMENT. 110-9
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372