2001-11-29 00:00:00 | CHECKLIST: |
| 1-REAR ELEVATION EXCEEDS THE MAXIMUM |
| AMOUNT OF OPENING PERCENTAGE ALLOWED |
| BY TABLE 600 OF SBC 1997. REVISE AS |
| REQUIRED. |
| 2-REVISE ENERGY CALCULATIONS: |
| -UNDER ATTIC AREA: SEE SEC. 604.1.A.1 |
| OF FLORIDA ENERGY CODE, 1997 ED. |
| -WALLS: THERE IS NOT EXT. FRAME WALL. |
| -REVISE # OF BEDROOMS: SEE BEDROOM |
| DEFINITION ON FL. ENERGY CODE, 1997 ED |
| 3-PROVIDE CURRENT UL ASSEMBLY # FOR ONE |
| HR FIRE RATED GLASS BLOCK ASSEMBLY. |
| 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| ENTRY DOORS. |
| 5-TRUSS DRAWINGS: |
| -UPDATE GENERAL DETAILS. USE ASCE 7-95 |
| FOR 140MPH, NOT ASCE 7-93 110MPH OR |
| USE SBC 1997 FOR 110 MPH. |
| -MAKE SURE ALL DETAILS AND NOTES ARE |
| LEGIBLE. |
| -REVIEW STAMP ON TRUSS LAYOUT DOESN'T |
| IDENTIFY THE FIRM WHO REVIEW ALL TRUSS |
| DRAWINGS. (NOTE: ENGINEER SHALL NOT |
| SIGN AND SEAL THESE DRAWINGS. ONLY THE |
| STANDARD REVIEW STAMP IS REQUESTED). |
| 6-SOIL TEST REPORT ENGINEER TO PROVIDE |
| ORIGINAL SIGNATURE AS REQUIRED BY |
| CHAPTER 471 OF FLORIDA STATUTES. |
| 7-SEE PLANS FOR ADDITIONAL COMMENTS. |