Plan Review Notes
Plan Review Notes For Permit 01101510
Permit Number 01101510
Review Stop R
Sequence Number 1
Notes
Date Text
2001-11-29 00:00:00CHECKLIST:
 1-REAR ELEVATION EXCEEDS THE MAXIMUM
 AMOUNT OF OPENING PERCENTAGE ALLOWED
 BY TABLE 600 OF SBC 1997. REVISE AS
 REQUIRED.
 2-REVISE ENERGY CALCULATIONS:
 -UNDER ATTIC AREA: SEE SEC. 604.1.A.1
 OF FLORIDA ENERGY CODE, 1997 ED.
 -WALLS: THERE IS NOT EXT. FRAME WALL.
 -REVISE # OF BEDROOMS: SEE BEDROOM
 DEFINITION ON FL. ENERGY CODE, 1997 ED
 3-PROVIDE CURRENT UL ASSEMBLY # FOR ONE
 HR FIRE RATED GLASS BLOCK ASSEMBLY.
 4-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ENTRY DOORS.
 5-TRUSS DRAWINGS:
 -UPDATE GENERAL DETAILS. USE ASCE 7-95
 FOR 140MPH, NOT ASCE 7-93 110MPH OR
 USE SBC 1997 FOR 110 MPH.
 -MAKE SURE ALL DETAILS AND NOTES ARE
 LEGIBLE.
 -REVIEW STAMP ON TRUSS LAYOUT DOESN'T
 IDENTIFY THE FIRM WHO REVIEW ALL TRUSS
 DRAWINGS. (NOTE: ENGINEER SHALL NOT
 SIGN AND SEAL THESE DRAWINGS. ONLY THE
 STANDARD REVIEW STAMP IS REQUESTED).
 6-SOIL TEST REPORT ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 7-SEE PLANS FOR ADDITIONAL COMMENTS.