2001-11-29 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO: WILL NEED THE ELEVATION
 CERTIFICATE.
 2-REVISE ENERGY CALCULATIONS:
 -REVISE UNDER ATTIC AREA. SEE SECTION
 604.1.A.1 FL. ENERGY CODE, 1997.
 3-PROVIDE CURRENT UL ASSEMBLY FOR FIRE
 RATED GLASS BLOCK ASSEMBLY.
 4-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ENTRY DOORS.
 5-PROVIDE STRUCTURAL HANGING DETAIL FOR
 AHU. SPECIFY ALL CONNECTORS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 6-REVISE WINDOW SIZE FOR BEDROOM #3:
 24 SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT OPENING REQUIRED BY
 SEC. 1005.4 SBC 1997.
 7-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 8-TRUSS DRAWINGS:
 -UPDATE GENERAL DETAILS. USE ASCE 7-95
 FOR 140 MPH NOT, ASCE 7-93 FOR 110MPH.
 -SEE GENERAL DETAILS FOR COMMENTS.
 -MAKE SURE ALL DETAILS ARE LEGIBLE.
 -REVIEW STAMP DOESN'T IDENTIFY THE
 NAME OF FIRM WHO REVIEWED ALL TRUSS
 DRAWINGS. ENGINEER OF RECORD DOESN'T
 NEED TO SEAL THE TRUSS LAYOUT. JUST
 USE THE STANDARD REVIEW STAMP.
 9-REVISE THE ROOF SHEATHING SPECS ON
 THE TYPICAL WALL SECTION. SEE SECTION
 2306 OF CITY AMENDMENTS TO SBC 1997.
 10-SOIL TEST REPORT ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.