Plan Review Notes
Plan Review Notes For Permit 01101462
Permit Number 01101462
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-29 00:00:00******************** UNSAT************
  
 1)NOTE: PLEASE NOTE ON PLANS THAT THE
 ELECTRICAL RISER SHOWN IS EXISTING.
  
 2)NOTE: PLEASE NOTE THAT ALL COMMERCIAL
 PLANS ARE TO HAVE BRANCH CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE NOTE THAT UNDER FS/FAC
 ALL PLANS THAT CONTAIN TITLE BLOCK(S)
 FOR ARCH/ENG OF RECORD, MUST BE SIGNED,
 DATED AND SEALED BY THAT PERSON.F.S.
 481.221/ 471.025.
  
 4)NOTE: PLEASE CLARIFY OTHER ELECTRICAL
 EXISTING? EXIT LTS, EM LTS ETC.
  
 5)NOTE: PLEASE NOTE THAT PLANS THAT
 PLANS NEED TO HAVE RECEPTS IN BATHS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372