Plan Review Notes
Plan Review Notes For Permit 01101438
Permit Number 01101438
Review Stop R
Sequence Number 2
Notes
Date Text
2002-01-22 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO. NEED THE ELEVATION
 CERTIFICATE.
 2-PROVIDE ENTRY DOORS PRODUCT APPROVAL
 WITH LEGIBLE DRAWINGS.
 3-ENGINEER OF RECORD TO REVISE THE
 STRUCTURAL BUCK DETAIL SHOWING A 2X
 BUCK DETAIL AS REQUIRED ON THE PRODUCT
 APPROVAL USED FOR ENTRY DOORS.
 4-TRUSS DRAWINGS 2ND REVIEW:
 *CONTRACTOR CHANGED TRUSS COMPANY.
 A)UPDATE ALL GENERAL TRUSS DETAILS.
 B)THERE ARE 2 ENGINNERS SEALING THE
 GENERAL TRUSS DETAILS. COMPLY WITH
 REQUIREMENTS OF FLORIDA ENGINEER BOARD
 WHEN AN ENGINEER'S TAKEN OTHER'S WORK.
 C)PROVIDE LEGIBLE & COMPLETE GENERAL
 TRUSS DETAILS.
 D)ENGINEERED TRUSSES ARE DESIGNED USING
 ASCE 7-98. NEED TO USE THE RIGHT WIND
 ZONE. IT IS 140MPH, NOT 110 MPH WIND.
 -ALSO, USE THE MEAN ROOF HEIGHT. THIS
 BLDG HAS AN SLOPED ROOF, NOT FLAT ROOF