2001-11-28 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO: NEED THE ELEVATION
 CERTIFICATE.
 2-REVISE ENERGY CALCULATIONS:
 -UNDER ATTIC AREA IS INCORRECT. SEE
 SECTION 604.1.A.1 OF FL. ENERGY CODE.
 -REVISE NUMBER OF BEDROOMS. SEE BEDRM
 DEFINITION ON FL. ENERGY CODE.
 3-GLASS BLOCK INFORMATION IS TOO OLD.
 YEAR 1992. PROVIDE CURRENT UL FIRE
 RATED ASSEMBLY NUMBER.
 4-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ENTRY DOORS.
 5-TRUSS DRAWINGS:
 -UPDATE GENERAL DETAILS. USE SBC 1997
 FOR 110MPH OR ASCE 7-95 FOR 140MPH.
 SEE COMMENTS ENGINEERED TRUSSES.
 -SOME DETAILS ARE NOT LEGIBLE.
 -REVIEW STAMP BY ENGINEER DOESN'T
 IDENTIFY THE FIRM WHO REVIEW THE TRUSS
 DRAWINGS. PROFESSIONAL ENGINEER OF
 RECORD DOESN'T HAVE TO SEAL THE TRUSS
 LAYOUT. HE ONLY NEEDS THE REVIEW STAMP,
 BUT IDENTIFYING HIS NAME OR COMPANY.
 6-PROVIDE STRUCTURAL HANGING DETAIL FOR
 AHU. SPECIFY ALL CONNECTORS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 7-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 8-REVISE THE ROOF SHEATHING SPECS ON TYP
 WALL SECTION. SEE SECTION 2306 OF CITY
 AMENDMENTS TO SBC 1997.
 9-SOIL TEST REPORT ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 10-REVISE SIZE OF WINDOW BEDROOM #3.
 24SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT REQUIREMENT OF
 SECTION 1005.4 SBC 1997.