2001-11-28 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE AO: NEED THE ELEVATION |
| CERTIFICATE. |
| 2-REVISE ENERGY CALCULATIONS: |
| -UNDER ATTIC AREA IS INCORRECT. SEE |
| SECTION 604.1.A.1 OF FL. ENERGY CODE. |
| -REVISE NUMBER OF BEDROOMS. SEE BEDRM |
| DEFINITION ON FL. ENERGY CODE. |
| 3-GLASS BLOCK INFORMATION IS TOO OLD. |
| YEAR 1992. PROVIDE CURRENT UL FIRE |
| RATED ASSEMBLY NUMBER. |
| 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| ENTRY DOORS. |
| 5-TRUSS DRAWINGS: |
| -UPDATE GENERAL DETAILS. USE SBC 1997 |
| FOR 110MPH OR ASCE 7-95 FOR 140MPH. |
| SEE COMMENTS ENGINEERED TRUSSES. |
| -SOME DETAILS ARE NOT LEGIBLE. |
| -REVIEW STAMP BY ENGINEER DOESN'T |
| IDENTIFY THE FIRM WHO REVIEW THE TRUSS |
| DRAWINGS. PROFESSIONAL ENGINEER OF |
| RECORD DOESN'T HAVE TO SEAL THE TRUSS |
| LAYOUT. HE ONLY NEEDS THE REVIEW STAMP, |
| BUT IDENTIFYING HIS NAME OR COMPANY. |
| 6-PROVIDE STRUCTURAL HANGING DETAIL FOR |
| AHU. SPECIFY ALL CONNECTORS. SECTION |
| 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| 7-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS AND SEC. 2405.2 SBC 1997. |
| 8-REVISE THE ROOF SHEATHING SPECS ON TYP |
| WALL SECTION. SEE SECTION 2306 OF CITY |
| AMENDMENTS TO SBC 1997. |
| 9-SOIL TEST REPORT ENGINEER TO PROVIDE |
| ORIGINAL SIGNATURE AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTES. |
| 10-REVISE SIZE OF WINDOW BEDROOM #3. |
| 24SH WINDOW DOESN'T PROVIDE THE 24" |
| MIN. CLEAR HEIGHT REQUIREMENT OF |
| SECTION 1005.4 SBC 1997. |