Plan Review Notes
Plan Review Notes For Permit 01101437
Permit Number 01101437
Review Stop R
Sequence Number 2
Notes
Date Text
2002-02-12 00:00:00CHECKLIST:
 1-REVISED ENERGY CALCULATIONS ARE WRONG
 AGAIN. SEE SQUARE FOOTAGES ENTERED FOR
 A/C AREA AND UNDER ATTIC AREA.
 -PROVIDE CORRECT UNDER ATTIC AREA AS
 REQUIRED BY SEC. 604.1.A.1 OF FLORIDA
 ENERGY EFFICIENCY CODE. 1997 ED.
 -NOTE: THIS IS A MODEL HOUSE. PREVIOUS
 ENERGY CALCULATIONS WERE DONE TO WORST
 CASE SCENARIO. NOW, THIS ONE IS NOT.
 CLARIFY IF USING WORST CASE SCENARIO
 OR IF ENERGY CALCULATIONS WILL BE
 CALCULATED FOR EACH HOUSE.
 2-PLANS SUBMITTED AT TIME OF APPLICATION
 SHOW GARAGE AT RIGHT HAND SIDE. NOW,
 PLANS RESUBMITTED SHOW GARAGE AT LEFT
 HAND SIDE. PROVIDE REVISED SURVEY FOR
 ZONING AND BUILDING RE-REVIEW.
 3-SPECIFY ON FLOOR PLAN 1 HR FIRE RATED
 GLASS BLOCK ASSEMBLY AT ZERO LOT LINE
 WALL AND REVISE GLASS BLOCK DETAILS ON
 SHEET 5 TO MATCH 1 HR ASSEMBLY AS PER
 UL LISTING. SEE ATTACHED COPY THAT WAS
 SUBMITTED BY CONTRACTOR.
 4-TRUSS DRAWINGS:
 A)TRUSS ENGINEER TO SIGN, SEAL AND DATE
 TRUSS LAYOUT.
 B)UPDATE GENERAL DETAILS AS REQUIRED.
 USE CURRENT CODES AND CORRECT MPH
 WIND LOAD.
 C)THERE ARE 2 ENGINEER'S SEALS ON
 GENERAL DETAILS. REVISE AS REQUIRED.
 D)GENERAL DETAILS ARE NOT LEGIBLE.
 E)SPECIFY ON ENGINEERED TRUSSES WHAT
 EDITION OF SBC WAS USED FOR DESIGN.
 IT SHALL BE SBC 1997.
 F)MIXING AND MATCHING ASCE 7-98 AND SBC
 1997 IS NOT ALLOWED. REVISE AS REQ'D.
 G)RIGHT WIND ZONE USING ASCE 7-98 IS
 140 MPH. REVISE AS REQUIRED.
 5-SPECIFY CEILING INSTALLATION AT FRONT
 AND BACK PORCH. SEE ASTM C-926 AND
 ASTM C-1063 AND PROVIDE SPECS AS REQ'D
 (SEC. 2504.2 SBC 1997).
 6-SEE COMMENTS ON PLANS.
 7-CLEARLY SPECIFY SIZE OF ANCHOR ON DWG
 3B. EG: HETA 16, 20 OR 24 ETC.