2001-11-28 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE AO: NEED TO PROVIDE THE |
| ELEVATION CERTIFICATE. |
| 2-REVISE ENERGY CALCULATIONS: |
| -UNDER ATTIC AREA IS INCORRECT. SEE |
| SECTION 604.1.A.1 OF FLORIDA ENERGY |
| EFFICIENCE CODE FOR BUILDING CONSTR. |
| 3-PROVIDE CURRENT UL ASSEMBLY # FOR |
| FIRE RATED GLASS BLOCK ASSEMBLY. |
| 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| ENTRY DOORS. |
| 5-PROVIDE STRUCTURAL HANGING DETAIL FOR |
| AHU. SPECIFY ALL CONNECTORS. |
| SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| 6-REVISE WINDOW SIZE FOR BEDROOM #3. |
| 24 SH WINDOW DOESN'T MEET THE MINIMUM |
| CLEAR HT. OPENING OF 24". SEC 1005.4 |
| 7-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS. |
| 8-TRUSS DRAWINGS: |
| -UPDATE GENERAL DETAILS. USE ASCE 7-95 |
| FOR 140MPH OR SBC 1997 FOR 110MPH. |
| -MAKE SURE ALL DETAILS ARE LEGIBLE. |
| -REVIEW STAMP BY ENGINEER OF RECORD |
| DOESN'T IDENTIFY THE FIRM WHO REVIEWED |
| THE TRUSS DRAWINGS. |
| NOTE: ENGINEER DOESN'T NEED TO SEAL |
| THE TRUSS LAYOUT. ONLY REVIEW |
| AKNOWLEDGMENT IS REQUIRED. |
| 9-SOIL TEST REPORT ENGINEER TO PROVIDE |
| ORIGINAL SIGNATURE, NOT RUBBER STAMP, |
| AS REQUIRED BY CHAPTER 471 FL STATUTES |
| 10-TYPICAL WALL SECTION: REVISE ROOF |
| SHEATHING SPECS. SEE SECTION 2306 OF |
| CITY AMENDMENTS TO SBC FOR MINIMUM |
| NAILING AND SPACING. |