Plan Review Notes
Plan Review Notes For Permit 01101437
Permit Number 01101437
Review Stop R
Sequence Number 1
Notes
Date Text
2001-11-28 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 2-REVISE ENERGY CALCULATIONS:
 -UNDER ATTIC AREA IS INCORRECT. SEE
 SECTION 604.1.A.1 OF FLORIDA ENERGY
 EFFICIENCE CODE FOR BUILDING CONSTR.
 3-PROVIDE CURRENT UL ASSEMBLY # FOR
 FIRE RATED GLASS BLOCK ASSEMBLY.
 4-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ENTRY DOORS.
 5-PROVIDE STRUCTURAL HANGING DETAIL FOR
 AHU. SPECIFY ALL CONNECTORS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 6-REVISE WINDOW SIZE FOR BEDROOM #3.
 24 SH WINDOW DOESN'T MEET THE MINIMUM
 CLEAR HT. OPENING OF 24". SEC 1005.4
 7-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS.
 8-TRUSS DRAWINGS:
 -UPDATE GENERAL DETAILS. USE ASCE 7-95
 FOR 140MPH OR SBC 1997 FOR 110MPH.
 -MAKE SURE ALL DETAILS ARE LEGIBLE.
 -REVIEW STAMP BY ENGINEER OF RECORD
 DOESN'T IDENTIFY THE FIRM WHO REVIEWED
 THE TRUSS DRAWINGS.
 NOTE: ENGINEER DOESN'T NEED TO SEAL
 THE TRUSS LAYOUT. ONLY REVIEW
 AKNOWLEDGMENT IS REQUIRED.
 9-SOIL TEST REPORT ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE, NOT RUBBER STAMP,
 AS REQUIRED BY CHAPTER 471 FL STATUTES
 10-TYPICAL WALL SECTION: REVISE ROOF
 SHEATHING SPECS. SEE SECTION 2306 OF
 CITY AMENDMENTS TO SBC FOR MINIMUM
 NAILING AND SPACING.