2002-01-19 00:00:00 | SUBMITTAL CHECKLIST: |
| 1-PROVIDE REVISED ENERGY CALCULATIONS. |
| THEY ARE REQUIRED FOR BUILDING PLAN |
| REVIEW ALSO. NOT ONLY FOR MECH. REVIEW |
| 2-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOORS. PRODUCT APPROVAL SUBMITTED IS |
| GOOD FOR WOOD FRAMED BUILDINGS ONLY, |
| NOT FOR MASONRY CONSTRUCTION. SEE |
| PRODUCT APPROVAL. |
| -PROVIDE PRODUCT APPROVAL WITH LEGIBLE |
| DRAWINGS AS WELL. |
| 3-TRUSS DRAWINGS 2ND REVIEW: |
| A)THERE ARE SEVERAL CODES MIXED IN THE |
| TRUSS DRAWINGS: SFBC, ASCE 7-98 AND |
| SBC 1997. REVISE AS REQUIRED. |
| B)ENGINEERED TRUSSES AREN'T FOLLOWING |
| NOTE SPECIFIED BY ENGINEER OF RECORD |
| ON SHEET 3A REGARDING 3 1/2" MINIMUM |
| BEARING AT MID POINT OF TRUSS. SEE |
| NOTE ON FRAMING PLAN AT REAR PORCH. |
| C)ENGINEERED TRUSSES CALL FOR 14 FT |
| ABOVE GROUND LEVEL. THIS APPLIES TO A |
| FLAT ROOF. SLOPED ROOF IS DESIGNED |
| ACCORDING TO THE MEAN ROOF HEIGHT, |
| WHICH IN THIS CASE IS 15'. SEE DWGS |
| BY DESIGNER OF RECORD AND REVISE AS |
| REQUIRED. |
| D)TRUSS LAYOUT USES ASCE 7-95. CLARIFY. |
| 4-ENGINEER OF RECORD TO SPECIFY |
| CONNECTOR THAT RESIST THE UPLIFT LOADS |
| CALCULATED FOR TRUSS HG3. |