Plan Review Notes
Plan Review Notes For Permit 01101423
Permit Number 01101423
Review Stop R
Sequence Number 3
Notes
Date Text
2002-01-19 00:00:00SUBMITTAL CHECKLIST:
 1-PROVIDE REVISED ENERGY CALCULATIONS.
 THEY ARE REQUIRED FOR BUILDING PLAN
 REVIEW ALSO. NOT ONLY FOR MECH. REVIEW
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS. PRODUCT APPROVAL SUBMITTED IS
 GOOD FOR WOOD FRAMED BUILDINGS ONLY,
 NOT FOR MASONRY CONSTRUCTION. SEE
 PRODUCT APPROVAL.
 -PROVIDE PRODUCT APPROVAL WITH LEGIBLE
 DRAWINGS AS WELL.
 3-TRUSS DRAWINGS 2ND REVIEW:
 A)THERE ARE SEVERAL CODES MIXED IN THE
 TRUSS DRAWINGS: SFBC, ASCE 7-98 AND
 SBC 1997. REVISE AS REQUIRED.
 B)ENGINEERED TRUSSES AREN'T FOLLOWING
 NOTE SPECIFIED BY ENGINEER OF RECORD
 ON SHEET 3A REGARDING 3 1/2" MINIMUM
 BEARING AT MID POINT OF TRUSS. SEE
 NOTE ON FRAMING PLAN AT REAR PORCH.
 C)ENGINEERED TRUSSES CALL FOR 14 FT
 ABOVE GROUND LEVEL. THIS APPLIES TO A
 FLAT ROOF. SLOPED ROOF IS DESIGNED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 WHICH IN THIS CASE IS 15'. SEE DWGS
 BY DESIGNER OF RECORD AND REVISE AS
 REQUIRED.
 D)TRUSS LAYOUT USES ASCE 7-95. CLARIFY.
 4-ENGINEER OF RECORD TO SPECIFY
 CONNECTOR THAT RESIST THE UPLIFT LOADS
 CALCULATED FOR TRUSS HG3.