2001-11-27 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO. NEED ELEVATION
 CERTIFICATE.
 2-REVISE ENERGY CALCULATIONS. THERE IS
 NO EXTERIOR WOOD FRAME WALL. ALSO, SEE
 BEDRM DEFINITION & REVISE # OF BEDRMS.
 3-GLASS BLOCK INFORMATION IS TOO OLD.
 IT'S WRITTEN IN 1992. PROVIDE CURRENT
 UL ASSEMBLY SYSTEM.
 4-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ENTRY DOORS.
 5-TRUSS DRAWINGS:
 A)UPDATE GENERAL DETAILS. USE SBC 1997
 FOR 110 MPH OR ASCE 7-95 FOR 140MPH.
 B)SOME GENERAL DETAILS ARE NOT LEGIBLE.
 C)IDENTIFY WHO REVIEW TRUSS DRAWINGS.
 ENGINEER OF RECORD DON'T NEED TO SEAL
 THIS DRAWING.
  
 6-TYPICAL WALL SECTION:
 -REVISE ROOF SHEATHING SPECS. SEE SEC.
 2306 OF CITY AMENDMENTS FOR MINIMUM
 NAIL SIZE AND SPACING ACCORDING TO
 THE ZONE.
 7-SOIL TEST ENGINEER TO PROVIDE ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.