Plan Review Notes For Permit 01101403 |
Permit Number |
01101403 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-31 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) PLANS SUBMITTED ARE UNCLEAR. UNABLE | | TO DO PLAN REVIEW. PLEASE SUBMIT A CLEAR | | DRAFTSMAN QUALITY SET OF PLANS TO DO THE | | PLAN REVIEW WITH. | | 2) SHOW ALL PIPE SIZES ON EACH SET OF | | RISER DIAGRAMS | | 3) WATER HEATER TO BE ACCESSIBLE. SHOW | | DETAILS. SEC 501.7 | | 4) WATER SERVICE SHALL HAVE A REDUCED | | PRESSURE BACKFLOW, TYPE AND LOCATION BY | | UTILITY DEPT. CALL 659-8000 EXT 2008 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|