Plan Review Notes For Permit 01101293 |
Permit Number |
01101293 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-12-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01101293 | | 400 NORTHPOINT PKWAY / 403 | | BUTTERS CONSSTRUCTION | | CONTACT: FRANK GAMBENO | | TEL: (954) 570-8111 | | FAX: (954) 570-8844 | | | | SBC= 1997 STANDARD BUILDING CODE | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | 1)- PLANS INDICATE A MERCANTILE OCCUPAN- | | CY.THE AMOUNT OF FLAMMABLE/ COMBUSTIBLE | | LIQUIDS EXCEEDS THE AMOUNTS ALLLOWABLE | | IN TABLE 308.2B, FOR SPRINKLERED BUILD- | | ING, NOT IN A CABINET. | | THE TYPE OCCUPANCY SHALL BE A "H2 OCCU- | | PANCY" DEFLAGRATION HAZARDS, CLASS I, | | II AND III-A FLAMMABLE OR COMBUSTIBLE | | LIQUIDS. | | | | 2)- 408.6 STORAGE OF HAZARDOUS PRODUC- | | TION MATERIAL | | ROOMS USED TO THE STORAGE OF HPM IN QUAN | | ITIES GREATER THAN SET FORTH IN TABLE | | 408.3.3.B EXCEPT FOR THE PERMITTED | | WITHIN A FABRICATION AREA, SHALL COMPLY | | WITH THE PROVISIONS OF NFPA 30 PROVIDED | | THAT THE AREA OF AN HPM CUTOFF ROOM | | SHALL NOT EXCEED 6,000 SQ. FT. | | | | TO COMPLY WITH SECTIONS 408.6.1-408.6.7 | | | | SEE NFPA 30 FOR ADDITIONAL INFORMATION. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X8412 |
|