Plan Review Notes For Permit 01101293 |
Permit Number |
01101293 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-07 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE A1 SPC TABLE 407 MINIMUM FACIL- | | ITIES REQUIRE 2 W/C'S AND 2 LAVS FOR | | FEMALES. | | 2) PAGE A4 HDCP RESTROOMS, DOORS SHALL | | NOT OPEN INTO CLEAR FLOOR SPACE OR UN- | | OBSTRUCTED TURNING RADIUS PER FACBC SEC | | 4.22.3. | | 3) PAGE A4 TOILET ELEVATIONS, W/C TO BE | | 1'6" TO C/L OFF FINISHED WALL. | | 4) PAGE P0.1 PLUMBING NOTES #13, AIR | | CHAMBERS ARE "QUICK FIX" AND IF INSTALL- | | ED SHALL COMPLY WITH SPC SEC 607.8.3 AND | | BE RECHARGEABLE AND ACCESSIBLE. WATER | | HAMMER ARRESTORS SHALL BE INSTALLED PER | | WH-PDI 201 AND MANUFACTURE INSTALL. INST | | AND BE PLACED CLOSE TO FIXTURE. | | 5) P2.1 CONDENSATE LINE, SHOW DETAIL OF | | SUPPORT FOR CONDENSATE LINE. SHOW HOW | | SUPPORTS ARE ATTACHED TO ROOF. PVC LINES | | SHALL BE PAINTED TO PROTECT PIPES FROM | | U.V. RAYS PER MANUF. SPECS. | | 6) PAGE P2.1 RPZ BACKFLOW REQUIRED TO BE | | INSTALLED NO HIGHER THAN 4' AFF TO BE | | ACCESSIBLE. DRAIN TO FLOOR SINK WITH | | TRAP PRIMER, OR TO MOP SINK INDIRECTLY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|