2001-11-05 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01101293 |
| 400 NORTHPOINT # 403 |
| CONT: BUTTERS CONT |
| (954) 570-8111 |
| |
| SBC= STANDARD BUILDING CODE |
| SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| |
| 1)- TO BE ABLE TO IDENTIFY THE TYPE OF |
| BUILDING OCCUPANCY, THE CITY REQUEST |
| ADDITIONAL INFORMATION, MSDS SHEETS FOR |
| THE VARIOUS CHEMICALS PAINTS, THINNERS, |
| SOLVENTS, THE QUANITIES OF EACH. DEPEND- |
| ING ON THIS INFORMATION AND SBC TABLE |
| 308.B THE CITY WILL BE ABLE TO DETERMINE |
| THE OCCUPANCY CLASS. |
| WILL THIS SPACE BE FIRE SPRINKLERED. |
| PLANS INDICATE THAT IT WILL BE SUBMIT |
| FIRE SPRINKLER LAYOUT, DROPPED CEILING |
| AREA INDICATE FIRE SPRINKLERS. |
| |
| 2)- WILL THE AREA ABOVE THE OFFICE SPACE |
| BE USED FOR STORAGE. |
| |
| 3)- WAREHOUSE (STORAGE AREA 108) HOW |
| WILL THE RAW AND FINISHED PRODUCT BE |
| STORED? HEIGHT OF RACKS?CLEAR HEIGTH |
| BETWEEN THE RACK AREA FOR STORAGE & |
| THE BOTTOM OF SPRINKLER HEAD? |
| |
| 4)- MIXING ROOM DETAIL "C", THIS DETAIL |
| INDICATES A LIQUID TIGHT CURB ON ALL 4 |
| SIDES OF THE ROOM, WILL THE CURB RUN |
| ALSO UNDERNEATH THE DOORWAYS? WHAT MATER |
| IAL WILL BE USED TO SEAL THE FLOOR AND |
| CURB? HOW WILL SPILLAGE BE REMOVED? |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096X8412 |