Plan Review Notes For Permit 01101288 |
Permit Number |
01101288 |
|
Review Stop |
FIRE |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2003-05-01 00:00:00 | *************DENIED********************* | | 1) SEPARATION WITHIN PARKING STRUCTURE | | SHALL BE FIRE RATED NOT LESS THAN TWO | | HOURS. | | | | 2) SMOKE EVACUATION SYSTEM WAS APPROVED | | NOT SMOKE CONTROL. | | | | NATE MCCRAY, CAPTAIN | | 659-8096, EXT 8497 | | 835-2910 |
|