Text |
2002-06-26 00:00:00 | REFERENCE RESPONSE LETTER DATED JUNE |
| 12, 2002. |
| |
| RESPONSE TO COMMENT #1: A 2 HR ENCLOSURE |
| WILL BE PROVIDED.SEE ARCHITECTURAL |
| PLANS SHEET A-6.02 FOR 2 HR ENCLOSURE. |
| |
| PLAN SHEET A-6.02-INDICATE STAIR RISER |
| & STAIR DETAIL, NO 2 HR ENCLOSURE |
| SHOWN.PLEASE REVISE MECHANICAL PLANS |
| WITH ANOTE INDICATING DUCT TO BE IN A |
| RATED SHAFT PLEASE PROVIDE HR RATING. |
| PLEASE REMOVE FIRE DAMPERS ON DUCT |
| THAT IS TO BE IN THE SHAFT. |
| |
| RESPONSE TO COMMENT 2B: A DRYER BOOSTER |
| FAN HAS BEEN ADDED TO ALL DRYERS. |
| |
| PLEASE NOTE SHOULD THE BOOSTER FAN BE |
| USED ON THE DRYER EXHAUST A MEANS OF |
| NOTIFICATION TO THE OWNER/TENANT WILL |
| BE REQUIRED SHOULD THE BOOSTER FAN |
| FAIL. |
| |
| RESPONSE TO COMMENT #4: AXUILIARY DRAIN |
| PANS WILL BE PROVIDED FOR ALL HORIZONTAL |
| HEAT PUMPS. SEE INSTALLATION DETAILS ON |
| SHEET AC-6. |
| |
| INDICATE ON THE PLAN WHAT WILL SERVE |
| AS PROTECTION FOR THE VERTICAL UNITS |
| SHOULD THE PRIMARY DRAIN BE RESTRICTED |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |