Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop M
Sequence Number 3
Notes
Date Text
2002-06-26 00:00:00REFERENCE RESPONSE LETTER DATED JUNE
 12, 2002.
  
 RESPONSE TO COMMENT #1: A 2 HR ENCLOSURE
 WILL BE PROVIDED.SEE ARCHITECTURAL
 PLANS SHEET A-6.02 FOR 2 HR ENCLOSURE.
  
 PLAN SHEET A-6.02-INDICATE STAIR RISER
 & STAIR DETAIL, NO 2 HR ENCLOSURE
 SHOWN.PLEASE REVISE MECHANICAL PLANS
 WITH ANOTE INDICATING DUCT TO BE IN A
 RATED SHAFT PLEASE PROVIDE HR RATING.
 PLEASE REMOVE FIRE DAMPERS ON DUCT
 THAT IS TO BE IN THE SHAFT.
  
 RESPONSE TO COMMENT 2B: A DRYER BOOSTER
 FAN HAS BEEN ADDED TO ALL DRYERS.
  
 PLEASE NOTE SHOULD THE BOOSTER FAN BE
 USED ON THE DRYER EXHAUST A MEANS OF
 NOTIFICATION TO THE OWNER/TENANT WILL
 BE REQUIRED SHOULD THE BOOSTER FAN
 FAIL.
  
 RESPONSE TO COMMENT #4: AXUILIARY DRAIN
 PANS WILL BE PROVIDED FOR ALL HORIZONTAL
 HEAT PUMPS. SEE INSTALLATION DETAILS ON
 SHEET AC-6.
  
 INDICATE ON THE PLAN WHAT WILL SERVE
 AS PROTECTION FOR THE VERTICAL UNITS
 SHOULD THE PRIMARY DRAIN BE RESTRICTED
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.