Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2002-07-25 00:00:00THE "WS VERTICAL" CENTRAL FIRE
 SPRINKLER HEAD TECHNICAL DATA SHEET
 INDICATES THAT THE USE AND THEIR
 INSTALLATION DOES NOT FOLLOW THE
 LISTED MANUFACTURER'S CRITERIA. SUFFOLK
 CONSTRUCTION WAS CONTACTED BY TELEPHONE
 ON 7.25.02 AND ADVISED OF THIS.
 THE DESIGNER'S ARE TO REVIEW THE
 TECHNICAL DATA SHEET PROVIDED FOR THESE
 FIRE SPRINKLER HEADS AND ENSURE THAT
 THE FIRE SPRINKLER HEADS ARE INSTALLED
 PROPERLY WITH REGARDS TO THEIR
 INTENDED USE AND LISTINGS.
  
 2) ALL FIRE ALARM DEVICES ARE TO
 ACTIVATE THE STAIRWELL PRESSURIZATION
 FANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910