Plan Review Notes For Permit 01101288 |
Permit Number |
01101288 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-07-19 00:00:00 | ************** NOTES **************** | | | | NOTES REDLINED ON PLANS FOR WATER | | HEATER DISCONNECTING MEANS. DISC MAY BE | | REQ`D. "LOCK OFF" DEVICE TO BE USED | | MUST BE REVIEWED BY THE CHEIF ELECTRICAL | | INSPECTOR AND MYSELF BEFORE INSTALLING. | | PLEASE CALL IF THERE ARE ANY QUESTIONS, | | OR A MEETING TO VERIFY DEVICE. | | DISC MAY BE SOMETHING AS SIMPLE AS A | | TWO POLE SWITCH. | | | | PLEASE ALSO NOTE THAT DOORS ON MAIN | | ELECTRICAL ROOM AND GENERATOR ROOM | | MUST OPEN OUTWARDS. | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|