Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop E
Sequence Number 3
Notes
Date Text
2002-07-19 00:00:00************** NOTES ****************
  
 NOTES REDLINED ON PLANS FOR WATER
 HEATER DISCONNECTING MEANS. DISC MAY BE
 REQ`D. "LOCK OFF" DEVICE TO BE USED
 MUST BE REVIEWED BY THE CHEIF ELECTRICAL
 INSPECTOR AND MYSELF BEFORE INSTALLING.
 PLEASE CALL IF THERE ARE ANY QUESTIONS,
 OR A MEETING TO VERIFY DEVICE.
 DISC MAY BE SOMETHING AS SIMPLE AS A
 TWO POLE SWITCH.
  
 PLEASE ALSO NOTE THAT DOORS ON MAIN
 ELECTRICAL ROOM AND GENERATOR ROOM
 MUST OPEN OUTWARDS.
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372