2002-04-20 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-24 CODE OF REGU-
 LATION (CFR) 100.205
 (C)(IV) DESIGN MAN.
  
 1) FROM PREVIOUS REVIEW, SHOW CLEAR
 FLOOR SPACE FOR ALL BATHROOMS AND KIT.
 FIXTURES PER DESIGN MANUAL.
 2) FROM PREVIOUS REVIEW, SHT L3.02,04.
 COMMENT ASKED TO SHOW PREVENTER LOCATION
 FOR WATER FEATURE, REPLY SAID NOTE WAS
 ADDED. PLEASE SHOW WHERE BACKFLOW WILL
 BE LOCATED.
 3) FROM PREVIOUS REVIEW, SHT P1,6 SHOW
 LOCATION OF BACK FLOW PREVENTERS, UNABLE
 TO FIND LOCATION FOR WATER FEATURES AND
 COOLING TOWER.
 4) FROM PREVIOUS REVIEW SHT P-11 VERTI-
 CAL SANITARY RISERS #5,#13 SEC 911 WET
 VENTS, NO MORE THAN 4 FIXTURE UNITS ON A
 2" WET VENT. PLEASE RECHECK THESE RISERS
 5) SECONDARY ROOF DRAINS?????????