| 1.PLEASE CLARIFY REVISED PLAN SHEET |
| AC-1,EXHAUST DUCT PENETRATES LOBBY |
| FLOOR & FIRST FLOOR.PLANS INDICATE |
| FIRE DAMPERS AT EACH PENETRATION. |
| PLAN SHEET AC-1 LOBBY LEVEL SHOWS |
| TOILET EXHAUST TERMINATING ON THIRD |
| FLOOR WITH FIRE DAMPERS AT FLOOR |
| PENETRATIONS.AS PER 1997 SMC 610.4 |
| DUCTS EXTENDING THROUGH MORE THAN |
| ONE FLOOR SHALL BE PROTECTED BY A |
| SHAFT ENCLOSURE. ALSO PLAN SHEET |
| AC-3 6" EXHAUST DUCT DOWN, NO FIRE |
| DAMPER OR SHAFT INDICATED. |
| |
| 2.DRYER & TOILET EXHAUST TERMINATING |
| AT THE BALCONY.THIS CAN ONLY BE |
| APPROVED IF THIS AREA IS OPEN TO THE |
| OUTDOORS.NO SCREEN ENCLOSURE OR |
| SLIDING GLASS DOORS PERMITTED. |
| AS PER 1997 SMC 501.3, THE AIR |
| REMOVED BY EVERY MECHANICAL EXHAUST |
| SYSTEM SHALL BE DISCHARGED OUTDOORS |
| AT A POINT WHERE IT WILL NOT CAUSE |
| A NUISANCE. |
| |
| PLEASE NOTE DRYER EXHAUST SHALL BE |
| A MINIMUM OF 4".THE MAXIMUM LENGTH |
| SHALL BE 25 FT FROM DRYER LOCATION |
| TO WALL CAP.5 FT DEDUCTION FOR |
| EACH 90 DEGREE RAD. & 2 1/2 FT FOR |
| EACH 45 DEGREE RAD. |
| |
| 3.TESTING FOR STAIRWELL PRESSURIATION |
| SHALL BE PREFORMED BY INDEPENDENT |
| TEST & BALANCE COMPANY. TEST WILL |
| CHECK PRESSURE DIFFERENTIAL WITH ALL |
| DOORS CLOSED & WITHTHE DOOR AT |
| LOWER LEVEL PROPPED OPEN AT APPROX. |
| 4" TO SIMILATE EXITING DURING AN |
| EMERGENCY SITUATION. |
| |
| 4.PLEASE NOTE AUXILIARY DRAIN PANS |
| WITH OVERFLOW PROTECTION BY MEANS OF |
| A FLOAT SWITCH OR SEPARATE DRAIN |
| LINE TERMINATING AT A CONSPICUOUS |
| POINT AS PER 1997 SMC 304.8.6.1. |
| |