Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-05-03 00:00:001) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON FIRE PROTECTION BACKFLOW DEVICES.
  
 2) OCCUPANCY SEPARATIONS AND FIRE
 RESISTANCE OF WALLS INDICATES A ONE HOUR
 FIRE SEPARATION BETWEEN THE GARAGE AND
 THE BUILDING. A TWO HOUR FIRE SEPARATION
 IS REQUIRED.
  
 3) SEVERAL DOORS INCLUDING EXIT DOORS
 SWING OVER THE PROPERTY LINES FOR THE
 BUILDING.
  
 4) HOW DO THE EXIT DOORS THAT TERMINATE
 ON THE SOUTH SIDE OF THE BUILDING INTO
 THE ALLEY NOT BECOME OBSTRUCTED OR
 BLOCKED.
  
 5) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING PAGE A4.02.
  
 6) THE PLAN REVIEW COMMENTS OMITTED THAT
 STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) ANY FIRE ALARM INITIATING DEVICE OR
 FIRE SPRINKLER HEAD ACTIVATIONS ARE TO
 INITIATE THE STAIRWELL PRESSURIZATION
 FANS.
  
 8) STAIR PRESSURIZATION IS 0.05 WATER
 COLUMN TO INCLUDE MAXIMUM ANTICIPATED
 STACK EFFECT FOR THE REST OF THE
 BUILDING.
  
 9) EIFS NOTED FOR BUILDING. PLEASE
 REVIEW APPENDIX F OF THE STANDARD
 BUILDING CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910