2002-04-17 00:00:00***************** NOTE***************
  
 1)NOTE: PLEASE CALRIFY NO CONCRETE
 ENCASEMENT SHOWN FOR SERVICE ENTRANCE
 INTO MAIN FEEDING "XDP". BACK TO BACK??
 PER LOCAL AMENDMENT 230-70
  
 2)NOTE: PLEASE CLARIFY THAT MAIN FIRE
 PUMP SERVICE RATED ATS HAS AN EXTERNAL
 MANUAL MEANS OF DISCONNECT. PLEASE NOTE,
 THAT NOTE FOR THIS EQUIPMENT MENTIONS
 AN EXTERNAL "SURGE SUPPRESSION", BUT
 NOTHING ABOUT MAIN. 230-76/230-79
 PLEASE NOTE THAT MAIN FEEDING "XDP"
 MENTIONS A MAIN CIRCUIT BREAKER, IS THIS
 THE SAME SET UP?
 PLEASE CLARIFY OCP FOR FIRE PUMP MAIN?
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT PLANS ARE IN
 GOOD SHAPE, BUT ARE COMING BACK FOR
 OTHER COMMENTS FROM OTHER REVIEWERS.
 IF THERE ARE ANY QUESTIONS/CLARIFICATION
 -S, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372