2002-04-17 00:00:00 | ***************** NOTE*************** | | | | 1)NOTE: PLEASE CALRIFY NO CONCRETE | | ENCASEMENT SHOWN FOR SERVICE ENTRANCE | | INTO MAIN FEEDING "XDP". BACK TO BACK?? | | PER LOCAL AMENDMENT 230-70 | | | | 2)NOTE: PLEASE CLARIFY THAT MAIN FIRE | | PUMP SERVICE RATED ATS HAS AN EXTERNAL | | MANUAL MEANS OF DISCONNECT. PLEASE NOTE, | | THAT NOTE FOR THIS EQUIPMENT MENTIONS | | AN EXTERNAL "SURGE SUPPRESSION", BUT | | NOTHING ABOUT MAIN. 230-76/230-79 | | PLEASE NOTE THAT MAIN FEEDING "XDP" | | MENTIONS A MAIN CIRCUIT BREAKER, IS THIS | | THE SAME SET UP? | | PLEASE CLARIFY OCP FOR FIRE PUMP MAIN? | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLEASE NOTE THAT PLANS ARE IN | | GOOD SHAPE, BUT ARE COMING BACK FOR | | OTHER COMMENTS FROM OTHER REVIEWERS. | | IF THERE ARE ANY QUESTIONS/CLARIFICATION | | -S, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|