2002-04-15 00:00:00 | AS NOTED ON THE 11/16/02 LIST OF CODE |
| COMMENTS, THE FLORIDA ACCESSIBILITY |
| CODE FOR BUILDING CONSTRUCTION, SECTION |
| 4.1.2 (5) REQUIRES SIX ACCESSIBLE |
| SPACES, SECTION 4.6.3 OF THE FACBC |
| REQUIRES |
| THEM TO BE TWELVE FEET WIDE WITH AN |
| ADJACENT FIVE FEET WIDE AISLE. PLEASE |
| REVISE AS NECESSARY. |
| |
| THE DOOR SCHEDULES DO NOT SHOW THE RATED |
| DOORS FOR THE ELEVATOR LOBBIES AS |
| REQUIRED BY SBC 412.6.1.(20 MINUTES) |
| |
| THE 4TH LEVEL FLOOR PLAN ON SHEET A2.06, |
| SHADED HATCHED AREA INDICATES A STEP AT |
| THE DOOR FROM ELEVATOR LOBBY #1 TO THE |
| SPA AREA.THIS IS PROHIBITED BY SBC |
| 1012.1.3. |
| |
| SHEET A4.02 IS STILL MISSING |
| INFORMATION FOR THE ATTACHMENT OF THE |
| PRECAST CONCRETE.SEE SBC 1403.2. |
| |
| THE PLANS DEPICT THE USE OF"EIFS" TRIM |
| IN VARIOUS PLACES.SBC F102.2.7 |
| REQUIRES ARCHITECTURAL TRIM TO BE OF |
| NON-COMBUSTIBLE OR FIRE RETARDANT |
| TREATED WOOD. |
| EIFS MEETS NEITHER OF THESE DESCRIPTIONS |
| |
| SHEET S19 INDICATES A COMBINATION OF |
| WIND TUNNEL TESTING AND THE ANALYTICAL |
| PROCEDURE.ASCE 7-95 SECTION 6.4.1.1 |
| REQUIRES THATONLY ONE OF THE |
| PROCEDURES BE USED. |
| |
| SHEET A6.01 SHOWS ROOF MOUNTED STAIR |
| PRESSURIZATION FAN.AC-1 SHOWS A SUPPLY |
| FAN AT THE LOBBY LEVEL.AC-6 SHOWS A |
| 4650 CFM SUPPLYDUCT AND A 2500 CFM |
| EXHAUST DUCT.PROVIDE CALCULATIONS AND |
| A NARRATIVE DESCRIBING THE SEQUENCE OF |
| OPERATION TO DEMONSTRATE COMPLIANCE WITH |
| SBC 412.11 (5) AS PREVIOUSLY REQUESTED. |
| |
| PLEASE PROVIDE THE DATA FOR THE |
| SPRINKLER HEADS THAT WILL PROVIDE AN |
| "EQUIVALENT ALTERNATE" FOR FIRE RATED |
| OPENING PROTECTIVES.SECTION 553.79 OF |
| THE FLORIDA STATUTES REQUIRES THE FIRE |
| PROTECTION INFORMATION TO BE ON THE |
| PERMIT PLANS AS WELL AS SBC 104.2 AND |
| NFPA 13 CHAPTER 6, (OR 8 IN THE 1999 |
| EDITION) |