Plan Review Notes For Permit 01101288 |
Permit Number |
01101288 |
|
Review Stop |
B |
Sequence Number |
18 |
|
Notes |
Date |
Text |
2004-01-27 00:00:00 | REVISIONS SHOWN AS #10 HAVING VARYING | | DATES. | | | | SHEET A 7.06 SPEAKS TO "NON-COMBUSTIBLE | | FOAM" WHICH HAS NOT BEEN ESTABLISHED TO | | DATE.THIS STATEMENT SHOULD BE REMOVED | | FROM THE PLANS SINCE THE PRODUCTS | | INSTALLED ON THE BUILDING TO DATE ARE | | NOT NON-COMBUSTIBLE AS DEFINED IN THE | | 1997 STANDARD BUILDING CODE OR THE 2001 | | FLORIDA BUILDING CODE. | | | | THE REQUESTED DOCUMENTS FOR THE | | ATTACHMENT METHODS USED FOR THE FOAM | | TRIM DEMONSTRATING WIND LOAD COMPLIANCE | | HAVE NOT BEEN PROVIDED.A COPY OF THE | | 11/06/03 REVIEW NOTES ARE ATTACHED. | | | | THE FIRE SPRINKLER PLANS DONOT CLEARLY | | REFLECT THE APPLICATION OF THE | | SPECIALTY FIRE SPRINKLER HEADS THAT | | WILL PROVIDE THE TWO HOUR FIRE RATING | | REQUIRED IN THE VARIANCE GRANTED BY THE | | BOARD OF ADJUSTMENTS. | | | | NO HEADS ARE SHOWN AT THE FIXED WINDOWS | | IN THE GUEST ROOMS. | | | | HEADS ARE SHOWN ON THE EXTERIOR SIDE OF | | THE BALCONY DOORS, BUT NOT AT THE | | INTERIOR SIDE. | | | | PLEASE REVISE AS NECESSARY. |
|