2004-01-27 00:00:00REVISIONS SHOWN AS #10 HAVING VARYING
 DATES.
  
 SHEET A 7.06 SPEAKS TO "NON-COMBUSTIBLE
 FOAM" WHICH HAS NOT BEEN ESTABLISHED TO
 DATE.THIS STATEMENT SHOULD BE REMOVED
 FROM THE PLANS SINCE THE PRODUCTS
 INSTALLED ON THE BUILDING TO DATE ARE
 NOT NON-COMBUSTIBLE AS DEFINED IN THE
 1997 STANDARD BUILDING CODE OR THE 2001
 FLORIDA BUILDING CODE.
  
 THE REQUESTED DOCUMENTS FOR THE
 ATTACHMENT METHODS USED FOR THE FOAM
 TRIM DEMONSTRATING WIND LOAD COMPLIANCE
 HAVE NOT BEEN PROVIDED.A COPY OF THE
 11/06/03 REVIEW NOTES ARE ATTACHED.
  
 THE FIRE SPRINKLER PLANS DONOT CLEARLY
 REFLECT THE APPLICATION OF THE
 SPECIALTY FIRE SPRINKLER HEADS THAT
 WILL PROVIDE THE TWO HOUR FIRE RATING
 REQUIRED IN THE VARIANCE GRANTED BY THE
 BOARD OF ADJUSTMENTS.
  
 NO HEADS ARE SHOWN AT THE FIXED WINDOWS
 IN THE GUEST ROOMS.
  
 HEADS ARE SHOWN ON THE EXTERIOR SIDE OF
 THE BALCONY DOORS, BUT NOT AT THE
 INTERIOR SIDE.
  
 PLEASE REVISE AS NECESSARY.