Plan Review Notes For Permit 01101288 |
Permit Number |
01101288 |
|
Review Stop |
P |
Sequence Number |
16 |
|
Notes |
Date |
Text |
2004-01-17 00:00:00 | REVISION DENITE | | REFERENCE: SPC-94 | | | | 1) SHT P-5 COOLING TOWER OVERFLOW SHALL | | DRAIN INTO THE STORM SYSTEM NOT THE | | SANITARY SYSTEM. | | 2) SHT P-11 SANITARY RISERS NUMBERS 6, | | AND 7. OFF SET VENTS REQUIRED PER SECT- | | ION 917. | | 3) SHT P-12 SANITARY RISERS NUMBERS 8, | | 11, 22, 23, 26, AND 28. OFFSET VENTS ARE | | REQUIRED PER SECTION 917. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|