Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop P
Sequence Number 16
Notes
Date Text
2004-01-17 00:00:00REVISION DENITE
 REFERENCE: SPC-94
  
 1) SHT P-5 COOLING TOWER OVERFLOW SHALL
 DRAIN INTO THE STORM SYSTEM NOT THE
 SANITARY SYSTEM.
 2) SHT P-11 SANITARY RISERS NUMBERS 6,
 AND 7. OFF SET VENTS REQUIRED PER SECT-
 ION 917.
 3) SHT P-12 SANITARY RISERS NUMBERS 8,
 11, 22, 23, 26, AND 28. OFFSET VENTS ARE
 REQUIRED PER SECTION 917.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]