Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop P
Sequence Number 12
Notes
Date Text
2003-07-21 00:00:00DENIED
 REFERENCE: SPC-94
 FACBC-97
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHT P-1 NOT SIGNED, SEALED, & DATED.
 2) SHT P-1A IS THIS A REVISION FOR ALL
 TYPICAL "B" UNITS OR FOR A SPECIFIC UNIT
 3) SHT P-4 NOT SIGNED, SEALED, & DATED.
 4) SHT P-7 NOT SIGNED, SEALED, & DATED.
 5) SHT P-7A NOT SIGNED, SEALED, & DATED.
 5) SHT P-7B NOT SIGNED, SEALED, & DATED.
 6) SHT P-9 NOT SIGNED, SEALED, & DATED.
 7) SHT P-10 NOT SIGNED, SEALED, & DATED.
 8) SHT P-11 NOT SIGNED, SEALED, & DATED.
 9) SHT P-11 OFFSETS FOR STACKS 1, 4, 5,
 6, A RELIEF VENT FOR THE OFFSET SHALL BE
 INSTALLED AS PROVIDED IN CHAPTER 9 AND
 IN NO CASE SHALL A HORIZONTAL BRANCH
 CONNECT WITHIN THE OFFSET OR WITHIN 2FT
 ABOVE OR BELOW THE OFFSET. THE RELIEF
 VENTS SHALL COMPLY WITH SECTIONS 917,
 917.1, 917.2 & 917.3. - SEC 715.4(4)
 10) SHT P-11A NOT SIGNED, SEALED, & DAT-
 ED. RISERS #11, 13, & 18. OFFSET VENTS
 REQUIRED SEC. 917 & ALL SUBSECTIONS. EX-
 TRA FIXTURE UNITS NOT REFLECTED ON RISER
 DIAGRAM.
 11) SHT P-12 RISERS 22, 23, 28, & 26 -
 OFFSET RELIEF VENTS REQUIRED PER SECTION
 917. ALSO SEE SECTION 715.4(4).
 12) SHT P-15 NOT SIGNED, SEALED, & DATED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692