2001-10-24 00:00:00 | 1) PLEASE BE ADVISED THAT THIS |
| BUILDING WILL BE LOCATED IN THE CITY |
| FIRE LIMITS. PLEASE BE ADVISED THAT |
| CERTAIN RESTRICTIONS APPLY TO |
| BUILDINGS LOCATED IN THESE LIMTS. |
| PLEASE SEE APPENDIX F OF THE STANDARD |
| BUILDING CODE AND CHAPTER 11 OF THE |
| CITY CODE. |
| 2) SEPARATION BETWEEN THE PARKING |
| GARAGE AND OTHER PORTIONS OF THE |
| BUILDING SHALL BE AT LEAST TWO HOURS |
| AND NOT ONE HOUR AS DEPICTED. |
| 3) WRONG LIFE SAFETY CODE REFERENCED |
| ON THE PLANS. SHOULD READ 1985 EDITION |
| INSTEAD OF 1997. |
| 4) FIRE HYDRANTS NOT SHOWN ON DRAWINGS. |
| 5) TEMPORARY STANDPIPES ARE REQUIRED |
| DURING CONSTRUCTION WHEN THE BUILDING |
| REACHES THREE STORIES AND FIFTY FEET |
| IN HEIGHT. ALSO EXIT STAIRS ARE TO BE |
| KEPT UP WITH CONSTRUCTION. |
| 6) PLEASE INDICATE LOCATION ON KNOX-BOX. |
| 7) PLEASE INDICATE COMPLIANCE WITH |
| STRETCHER REQUIREMENTS OF THE STANDARD |
| BUILDING CODE. |
| 8) FIRE COMMAND ROOM SHALL CONTAIN |
| ALL OF THE PRESCRIPTIVE REQUIREMENTS |
| OF THE STANDARD BUILDING CODE. |
| 9) PLEASE EXPLAIN PURPOSE OF GATES AT |
| STAIRS ON THE ROOF. |
| 10) PLEASE INDICATE ON THE PLANS THE |
| NUMBER OF AIR CHANGES REQUIRED FOR THE |
| CLOSED PARKING GARAGE. ALSO INDICATE |
| AIR EXHAUST VOLUMES. |
| 11) BUILDING ADDRESS REQUIRED PER CITY |
| CODE 3343-00. |
| 12) CANVAS CANOPIES TO BE FIRE |
| RETARDANT. |
| 13) PLEASE VERIFY THAT THE FIRE |
| SPRINKLER HEADS PLANNED FOR USE ARE NOT |
| ON THE VOLUNTARY RECALL LIST PROVIDED. |
| 14) PLEASE INDICATE WHAT THE VOICE |
| EVACUATION MESSAGE WILL SAY FOR THE |
| FIRE ALARM SYSTEM. |
| 15) PLEASE FURTHER EXPLAIN # 15 ON DOOR |
| SCHEDULE NOTES. |
| 16) HOW IS EXITING DIMINISHED WHEN THE |
| GARAGE DOORS ARE CLOSED. |
| 17) PLEASE INDICATE WHAT THE HANDRAILS |
| AND GUARDRAILS RATED FOR. |
| 18) PLEASE PROVIDE MORE INFORMATION ON |
| THE INSULATION PLANNED FOR USE ON THE |
| TRASH-CHUTE. |
| 19) PLEASE EXPLAIN WHY NO FIRE SPRINKLER |
| HEADS ARE SHOWN IN THE WALKWAY AREA. |
| 20) NO PENETRATIONS ALLOWED IN THE |
| STAIRWELLS EXCEPT FOR EMERGENCY LIGHTING |
| AND FIRE PROTECTION SYSTEMS. |
| 21) PLEASE DEMONSTRATE COMPLAINCE FOR |
| SEPARATION OF EXITS. |
| 22) PLEASE PROVIDE TESTING CRITERIA FOR |
| THE STAIRWELL PRESSURIZATION EQUIPMENT |
| CONTAINED WITHIN THE BUILDING. |
| 23) FIRE SPRINKLER DRAWINGS HAVE FIRE |
| COMMAND ROOM AND VALET ROOM SWITCHED. |
| 24) CONDUIT SHAFTS ARE TO BE PROPERLY |
| FIRE RATED. PLEASE INDICATE THIS ON |
| THE PLANS. |
| 25) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FIRE SPRINKLER SYSTEMS AND FIRE |
| ALARM SYSTEMS. |
| 26) ELEVATORS TO COMPLY WITH ANSI A17.1. |
| 27) HOW IS COMBUSTIBLE LINT REMOVED FROM |
| DRYER EXHAUST VENTS. |
| 28) ARE POOL CHEMICALS PLANNED TO BE |
| STORED IN POOL EQUIPMENT ROOMS. |
| 29) ANY CHANGES IN ELEVATIONS LESS THAN |
| 21 INCHES SHALL BE BY RAMPS. |
| 30) FIRST FLOOR RETAIL SPACES ARE TO |
| MEET MINIMUM FIRE SAFETY REQUIREMENTS |
| PRIOR TO BUILDING RECEIVING APPROVALS. |
| 31) PLEASE DEMONSTRATE COMPLIANCE WITH |
| SMOKE CONTROL REQUIREMENTS FROM THE |
| STANDARD BUILDING CODE. |
| 32) WHAT WILL THE ACCESS PANEL DOOR |
| BELOW THE MECHANICAL ROOM METAL |
| ACCESS STAIR BE USED FOR. |
| |
| MIKE CARSILLO, CAPTAIN |
| 659-8096,EXT.8497 |
| 835-2910 |