Plan Review Notes
Plan Review Notes For Permit 01101288
Permit Number 01101288
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-10-24 00:00:001) PLEASE BE ADVISED THAT THIS
 BUILDING WILL BE LOCATED IN THE CITY
 FIRE LIMITS. PLEASE BE ADVISED THAT
 CERTAIN RESTRICTIONS APPLY TO
 BUILDINGS LOCATED IN THESE LIMTS.
 PLEASE SEE APPENDIX F OF THE STANDARD
 BUILDING CODE AND CHAPTER 11 OF THE
 CITY CODE.
 2) SEPARATION BETWEEN THE PARKING
 GARAGE AND OTHER PORTIONS OF THE
 BUILDING SHALL BE AT LEAST TWO HOURS
 AND NOT ONE HOUR AS DEPICTED.
 3) WRONG LIFE SAFETY CODE REFERENCED
 ON THE PLANS. SHOULD READ 1985 EDITION
 INSTEAD OF 1997.
 4) FIRE HYDRANTS NOT SHOWN ON DRAWINGS.
 5) TEMPORARY STANDPIPES ARE REQUIRED
 DURING CONSTRUCTION WHEN THE BUILDING
 REACHES THREE STORIES AND FIFTY FEET
 IN HEIGHT. ALSO EXIT STAIRS ARE TO BE
 KEPT UP WITH CONSTRUCTION.
 6) PLEASE INDICATE LOCATION ON KNOX-BOX.
 7) PLEASE INDICATE COMPLIANCE WITH
 STRETCHER REQUIREMENTS OF THE STANDARD
 BUILDING CODE.
 8) FIRE COMMAND ROOM SHALL CONTAIN
 ALL OF THE PRESCRIPTIVE REQUIREMENTS
 OF THE STANDARD BUILDING CODE.
 9) PLEASE EXPLAIN PURPOSE OF GATES AT
 STAIRS ON THE ROOF.
 10) PLEASE INDICATE ON THE PLANS THE
 NUMBER OF AIR CHANGES REQUIRED FOR THE
 CLOSED PARKING GARAGE. ALSO INDICATE
 AIR EXHAUST VOLUMES.
 11) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 12) CANVAS CANOPIES TO BE FIRE
 RETARDANT.
 13) PLEASE VERIFY THAT THE FIRE
 SPRINKLER HEADS PLANNED FOR USE ARE NOT
 ON THE VOLUNTARY RECALL LIST PROVIDED.
 14) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE WILL SAY FOR THE
 FIRE ALARM SYSTEM.
 15) PLEASE FURTHER EXPLAIN # 15 ON DOOR
 SCHEDULE NOTES.
 16) HOW IS EXITING DIMINISHED WHEN THE
 GARAGE DOORS ARE CLOSED.
 17) PLEASE INDICATE WHAT THE HANDRAILS
 AND GUARDRAILS RATED FOR.
 18) PLEASE PROVIDE MORE INFORMATION ON
 THE INSULATION PLANNED FOR USE ON THE
 TRASH-CHUTE.
 19) PLEASE EXPLAIN WHY NO FIRE SPRINKLER
 HEADS ARE SHOWN IN THE WALKWAY AREA.
 20) NO PENETRATIONS ALLOWED IN THE
 STAIRWELLS EXCEPT FOR EMERGENCY LIGHTING
 AND FIRE PROTECTION SYSTEMS.
 21) PLEASE DEMONSTRATE COMPLAINCE FOR
 SEPARATION OF EXITS.
 22) PLEASE PROVIDE TESTING CRITERIA FOR
 THE STAIRWELL PRESSURIZATION EQUIPMENT
 CONTAINED WITHIN THE BUILDING.
 23) FIRE SPRINKLER DRAWINGS HAVE FIRE
 COMMAND ROOM AND VALET ROOM SWITCHED.
 24) CONDUIT SHAFTS ARE TO BE PROPERLY
 FIRE RATED. PLEASE INDICATE THIS ON
 THE PLANS.
 25) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEMS AND FIRE
 ALARM SYSTEMS.
 26) ELEVATORS TO COMPLY WITH ANSI A17.1.
 27) HOW IS COMBUSTIBLE LINT REMOVED FROM
 DRYER EXHAUST VENTS.
 28) ARE POOL CHEMICALS PLANNED TO BE
 STORED IN POOL EQUIPMENT ROOMS.
 29) ANY CHANGES IN ELEVATIONS LESS THAN
 21 INCHES SHALL BE BY RAMPS.
 30) FIRST FLOOR RETAIL SPACES ARE TO
 MEET MINIMUM FIRE SAFETY REQUIREMENTS
 PRIOR TO BUILDING RECEIVING APPROVALS.
 31) PLEASE DEMONSTRATE COMPLIANCE WITH
 SMOKE CONTROL REQUIREMENTS FROM THE
 STANDARD BUILDING CODE.
 32) WHAT WILL THE ACCESS PANEL DOOR
 BELOW THE MECHANICAL ROOM METAL
 ACCESS STAIR BE USED FOR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910