Plan Review Notes For Permit 01101288 |
Permit Number |
01101288 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-06 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE CLARIFY HOW FEEDS ARE | | COMING INTO "HDP" AND TO "TDP" PLEASE | | NOTE THEY DON'T BACK UP TO TRANSFORMER | | VAULT AND OTHER SERVICE ENTRANCE CONDUCT | | -ORS ARE ENCASED IN CONCRETE. | | PLEASE NOTE THAT NO MORE THAN 8' OF | | UN PROTECTED CONDUCTORS ARE ALLOWED | | "INSIDE" THE BLDG. PER LOCAL AMENDMENT; | | 230-70. | | | | 2)NOTE: PLEASE SUBMIT SCHEDULE FOR "HDP" | | ? | | | | | | | | | | 4)NOTE: PLEASE CLARIFY MANUAL MEANS OF | | DISCONNECT AT ATS FROM FPL SERVICE, | | 230-76,230-79 | | PLEASE ALSO SHOW OCP FROM FPL LINE SIDE | | | | | | 5)NOTE: PLEASE CLARIFYKW RATING FOR | | GENERATOR AND LOAD ? SEEMS LOAD SHOWN | | EXCEEDS GENERATOR RATING OF 833AMPS. | | | | 6)NOTE: OCP FOR WATER HEATERS ON PANELS | | "HB" AND "HR". PLEASE NOTE 3KW WITH 30A | | OCP. 422-11 MIN 125% MAX 150%. | | PLEASE ADJUST. | | | | PLEASE SUBMIT THE ABOVEINFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|