2001-11-16 00:00:00 | THE SHEET TITLED TABULAR DATA NOTES 3 |
| HANDICAP PARKING SPACES USING THE |
| FORMULA OF 2% OF THE TOTAL.THAT IS |
| INCORRECT.THE FACBC 4.1.2 (5) |
| REQUIRES A MINIMUM OF 5 SPACES FOR |
| PARKING LOTS HAVING 101 TO 150 TOTAL |
| SPACES. |
| |
| SHOW THE VAN ACCESSIBLE SPACE REQUIRED |
| BY FACBC 4.1.2 (5) (B). |
| |
| SHEET A2.01 SHOWS THE HC SPACES PROPOSED |
| TO BE 8'-8" WIDE.THE FACBC 4.6.3 |
| MANDATES 12' WIDE PARKING SPACES. |
| PLEASE REVISE AS NECESSARY.SEE ALSO 4. |
| 6.5 FOR VERTICAL CLEARANCES. |
| |
| SHEET A2.01EGRESS FROM THE PARKING |
| SPACES ON THE WEST SIDE RAMP DOES NOT |
| COMPLY WITH SBC 1004.1.3, COMMON PATH |
| OFTRAVEL TO AND EXIT MUST BE 75' OR |
| LESS.THE ROLL DOWN DOOR DOES NOT |
| COMPLY WITHSBC 1012.1 AND THEREFORE IS |
| NOT AN EXIT. REVISE AS NECESSARY. |
| |
| SHEET A2.02. HANDRAILS ARE REQUIRED ON |
| THE RAMP IN STAIR #1.SEE SBC 1013.6. |
| |
| SHEET A2.01.SBC 412.6.1 REQUIRES |
| ELEVATOR LOBBIES FOR ALL ELEVATORS ON |
| ALL FLOORS W/ CERTAIN EXCEPTIONS.THE |
| GARAGE LEVELS, THE 4TH LEVEL SPA DECK |
| ELEVATOR #1 AND THE SERVICE ELEVATOR |
| WEST SIDE ON FLOORS 5 THROUGH 15 DO NOT |
| QUALIFY FOR THE EXCEPTION.REVISE AS |
| NECESSARY. |
| |
| THE INDIVIDUAL APARTMENTS MUST COMPLY |
| WITH SBC 412.6.2, ACCESS TO AN EXIT |
| WITHOUT TRAVEL THROUGH AN ELEVATOR |
| LOBBY. |
| |
| STAIRS #1 AND #2 DO NOT MEET THE 1/2 |
| DIAGONAL DISTANCE SEPARATION |
| REQUIREMENT OF SBC 1004.1.4. ON ALL |
| FLOORS WITH THE EXCEPTION OF THE |
| SUBTERRANEAN LEVEL.PLEASE REVISE AS |
| NECESSARY. |
| |
| SHEET A6.02 NOTES, CALLS FOR THE STAIRS |
| TO COMPLY WITH THE SFBC.PLEASE REVISE |
| TO INCLUDE AND ENSURE COMPLIANCE WITH |
| THE 1997 SBC. |
| |
| SHEET A3.07 DOOR NOTES #3. UNDERCUTTING |
| OF FIRE RATED DOORS MUST BE IN |
| ACCORDANCE WITH NFPA 80. |
| |
| SHOW A SPECIFIC CONNECTION DETAIL FOR |
| THE PRECAST STONE DEPICTED ON SHEET |
| 4.02 AND ELSEWHERE.IF THE DESIGN IS |
| DELEGATED TO A SPECIALTY ENGINEER |
| INDICATE THE LOCATION, NATURE, |
| MAGNITUDE AND DIRECTION OF THE FORCES |
| TO BE RESISTED.SEE SBC 104.2. |
| |
| THE EIFS SHOWN IN DETAIL #50, SHEET |
| A7.05 MUST COMPLY WITH SBC 1404.3 |
| AND SBC APPENDIX F102.7.REVISE AS |
| NECESSARY. |
| |
| SHEET A705 DETAIL 53.WHAT IS THE |
| PARAPET HEIGHT THAT SERVES AS A |
| GUARDRAIL?THE REFERENCE TO THE |
| LANDSCAPE PAGES IS NOT CLEAR.SEE SBC |
| 1015. |
| |
| SHEET A6.05.PROVIDE CALCULATIONS FOR |
| THE GUARDRAIL AT THE WINDOW |
| DEMONSTRATING COMPLIANCE WITH SBC |
| 1608.2.3. |
| |
| GIVEN THE CITY'S REQUIREMENT FOR |
| HURRICANE MISSILE IMPACT GLAZING, HOW |
| WILL COMPLIANCE WITH SBC 1405 BE |
| ACCOMPLISHED?PARTICULARLY, BUT NOT |
| LIMITED TO, GARAGE |
| LEVELS 2 AND 3. |
| |
| SHEET S18 CITES THE SFBC FOR DESIGN OF |
| RAILS.DESIGN MUST BE TO SBC 1997 WITH |
| SPECIFIC DESIGN CRITERIA AND NOT A CODE |
| SECTION.SEE SBC 104.2.1. |
| |
| SHEET S19 STRUCTURAL LOADS, DECLARES |
| THAT THAT STRUCTURAL ANALYSIS IS PER |
| ASCE 7-95 AND THAT COMPONENTS AND |
| CLADDING IS BY WIND TUNNEL TESTING. |
| ASCE 7-95 6.4.1.1 PROHIBITS THE MIXING |
| OF THE METHODS ANALYSIS.IT APPEARS |
| THAT THIS SITE IS SUBJECT TO UPWIND |
| OBSTRUCTIONS, CHANNELING, BUFFETING, |
| ETC. AS DESCRIBED IN SECTION 6.4.2.1 |
| LIMITATIONS OF ANALYTICAL PROCEDURE, |
| THAT A COMPLETE WIND TUNNEL |
| INVESTIGATION IS IN ORDER. |
| |
| SHOW THE DESIGN LOADS FOR THE WALKS |
| ALONG THE ARC FORMED ON GRID LINE 4, |
| SUBTENDED BY GRID LINE B, IN ACCORDANCE |
| WITH SBC 1604.9. |
| |
| PROVIDE A NARRATIVE FOR THE METHODS OF |
| TESTING REQUIRED BY SBC 412.1.2 FOR |
| SMOKE REMOVAL AND STAIR PRESSURIZATION |
| ON THE STANDBY POWER SYSTEM. |
| |
| SHEET E10 FIRE ALARM, DOES NOT SHOW THE |
| APARTMENT UNIT SMOKE DETECTORS LINKED |
| INTO THE SYSTEM AS PROVIDED FOR IN SBC |
| 412.2.2 AND SBC 412.2.1 (5). |
| |
| PLEASE PROVIDE CALCULATIONS |
| DEMONSTRATING COMPLIANCE WITH SBC |
| 412.11 (5) IF THAT IS THE INTENDED |
| OPTION OR COMPLY WITH SBC 1005.6. |
| |
| THE CONSTRUCTION BOARD OF ADJUSTMENTS |
| AND APPEALS GRANTED TWO VARIANCES AT |
| THEIR MAY 10, 2001 MEETING.ONE OF THE |
| STIPULATIONS OF THE BOARD WAS THAT "THE |
| SPRINKLER HEADS MEET THE RATING |
| REQUIREMENTS"AND BE OF AN "EQUIVALENT |
| ALTERNATE" PLEASE PROVIDE |
| TESTING |
| FROM A RECOGNIZED SOURCE THAT |
| DEMONSTRATES COMPLIANCE WITH SBC |
| 705.1.3 (NFPA 80) FOR THE SPRINKLERS. |
| |
| PROVIDE CALCULATIONS DEMONSTRATING |
| COMPLIANCE WITH 411.4.2 FOR THE SIX AIR |
| CHANGES PER HOUR IN THE GARAGE. |
| |
| THE SP DRAWINGS SHOW A RISER/STANDPIPE |
| IN A STAIR #3.WHAT IS THE INTENT OF |
| THIS? |