Plan Review Notes For Permit 01101268 |
Permit Number |
01101268 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-05 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE A-2 PRIVATE TOILET ROOM FOR THE | | OCCUPANT OF A PRIVATE OFFICE SHALL BE | | ADAPTABLE PER FACBC SEC 4.1.3(11). | | PLEASE SHOW DETAILS OF COMPLIANCE. SHOW | | HOW 20 PERCENT OVER CONTRACT IS SPENT | | FOR ADA PER SEC 4.6.1(2). | | 2) PAGES A-1 & P-1. GREASE TRAP TO BE | | DRAINED, TOP REMOVED, HOLE CUT IN BOTTOM | | INSPECTED, THEN CLEAN FILL PUT IN BEFORE | | BURYING. | | 3) SEPARATE DEMO PERMIT FOR DWV, WATER, | | GAS AND GREAS TRAP. | | 4) PAGES A-2 & A-6. SINK IN BREAK ROOM | | SHALL COMPLY WITH FACBC SEC 4.24. PLEASE | | PROVIDE DETAILS. | | 5) SPC TABLE 407 REQUIRES THAT A DRINK- | | ING FOUNTAIN BE INSTALLED. IF A SINGLE | | FOUNTAIN IS INSTALLED THEN PROVISIONS | | SHALL BE MADE FOR THOSE WHO HAVE DIFFIC- | | ULITY BENDING OR STOOPING PER FACBC SEC | | 4.1.3(10). PLEASE SUBMIT DETAILS FOR | | DRINKING FOUNTAIN PER FABCB SEC 4.15 | | ALSO. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|