Plan Review Notes
Plan Review Notes For Permit 01101224
Permit Number 01101224
Review Stop P
Sequence Number 8
Notes
Date Text
2003-12-01 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P400, PIPE SIZES FOR GAS LINES
 ARE INCORRECT. PLEASE CHANGES PIPES
 SIZES TO CORRECT PIPE SIZES SHOWN IN RED
 ON REVISION. ALSO SHOW ALL VALVES AT THE
 APPLIANCES.
 2) PER RULING BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS, A SIGNATURE IS
 REQUIRED ON SIGNED AND SEALED PLANS. IN-
 ITIALS ARE NOT ACCEPTED. 61G15-23.002(1)
 3) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THORUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF AUTH-
 ORIZATION NUMBER OF THE ENGINEERING BUS-
 INESS ON EACH SHEET. 61G15-23.002(2)
 SEE ATTACHED SHEET... FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]