Plan Review Notes For Permit 01101224 |
Permit Number |
01101224 |
|
Review Stop |
P |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2003-06-17 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) SHT P400 NATURAL GAS RISER DOES NOT | | REFLECT THE GAS APPLIANCE SCHEDULE. | | RISER SHOWS 200MBTUH FOR BBQ AND SCHED. | | SHOWS 69MBTUH. RISER SHOWS 200MBTUH FOR | | THE RANGE AND SCHED. SHOWS 144MBTUH. | | PLEASE CLAIRFY. | | 2) PLEASE INDICATE TYPE OF PIPE FOR EACH | | SECTION OF THE RISER. ALSO SHOW ALL PIPE | | SIZES FOR THE RISER SECTIONS AND DROPS. | | 3) SHT P100 INDICATES REVISIONS #4 & #5. | | PREVIOUS REVISION SHOWS #3 TO BE THE | | LAST REVISION. #4 NOT FOUND ON LATEST | | REVISION. PLEASE CLAIRFY. | | 4) SHT P400 INDICATES REVISIONS #2 & #3. | | PREVIOUS REVISION SHOWS #1 TO BE THE | | LAST REVISION. #2 NOT FOUND ON LATEST | | REVISION. PLEASE CLAIRFY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|