Plan Review Notes For Permit 01101224 |
Permit Number |
01101224 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-04-08 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION AND MAKE NECESSARY CHANGES | | ON PLANS AND RESUBMIT FOR REVIEW. | | | | 1} PANEL "A" MUST COMPLY WITH 230-70 WPB | | AMMENDMENTS.LOCATION OF THE DISCONNECT | | AT NEAREST POINT OF ENTRY,SEE NOTE #3 | | LAST REVIEW.GROUND PER 250-32. | | | | 2} THE OVEN LISTED ON THE LOAD CALCS | | MUST COMPLY WITH TABLE 220-19,OR | | CORRESPONDING NOTES. PLEASE CLARIFY HOW | | 5KW WAS DERIVED. | | | | 3} PANEL "B" IS REQUIRED TO HAVE A NAIN | | MEANS OF DICONNECT PER 230-71. | | | | 4} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|