Plan Review Notes For Permit 01101224
Permit Number 01101224
Review Stop E
Sequence Number 4
Notes
Date Text
2003-04-08 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE NECESSARY CHANGES
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} PANEL "A" MUST COMPLY WITH 230-70 WPB
 AMMENDMENTS.LOCATION OF THE DISCONNECT
 AT NEAREST POINT OF ENTRY,SEE NOTE #3
 LAST REVIEW.GROUND PER 250-32.
  
 2} THE OVEN LISTED ON THE LOAD CALCS
 MUST COMPLY WITH TABLE 220-19,OR
 CORRESPONDING NOTES. PLEASE CLARIFY HOW
 5KW WAS DERIVED.
  
 3} PANEL "B" IS REQUIRED TO HAVE A NAIN
 MEANS OF DICONNECT PER 230-71.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW