Plan Review Notes For Permit 01101224 |
Permit Number |
01101224 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-08 00:00:00 | *******************DENIED*************** | | | | | | 1.LOCATION OF TOILET EXHAUST ON THE | | FIRST FLOOR.PLAN INDICATES EXHAUST | | DUCT IS RUNNING IN CRAWL SPACE TO | | WALL CAP.PLEASE SPECIFY MATERIAL | | USED FOR EXHAUST DUCT.EXHAUST | | TERMINATION SHALL BE 10' FROM ANY | | WINDOW, DOOR OR FRESH AIR INTAKE AS | | PER 1997 SMC 506.1 OR 2' ABOVE FRESH | | AIR INTAKE. | | | | 2.DUCT IN CRAWL SPACE UNDER FIRST | | FLOOR SHALL NOT BE INSTALLED IN OR | | WITHIN 4 INCHES OF THE GROUND AS PER | | 1997 SMC 605.4. | | | | 3.PLEASE SPECIFY MATERIAL AND R-VALUE | | OF ALL DUCTWORK BEING INSTALLED. | | | | 4.INDICATE SIZE LOCATION OF LIQUID AND | | SUCTION REFRIGERANT LINES. | | | | 5.INDICATE LOCATION OF CONDENSER | | UNITS.PLAN SHEET A000 SHOWS COND. | | UNITS IN EXCESS OF 30' FROM THE | | HOUSE.PLEASE REFER TO MANUFACTURER | | INSTALLATION INSTRUCTIONS FOR LINE | | SIZE FOR THIS DISTANCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|