Plan Review Notes
Plan Review Notes For Permit 01101224
Permit Number 01101224
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-08 00:00:00*******************DENIED***************
  
  
 1.LOCATION OF TOILET EXHAUST ON THE
 FIRST FLOOR.PLAN INDICATES EXHAUST
 DUCT IS RUNNING IN CRAWL SPACE TO
 WALL CAP.PLEASE SPECIFY MATERIAL
 USED FOR EXHAUST DUCT.EXHAUST
 TERMINATION SHALL BE 10' FROM ANY
 WINDOW, DOOR OR FRESH AIR INTAKE AS
 PER 1997 SMC 506.1 OR 2' ABOVE FRESH
 AIR INTAKE.
  
 2.DUCT IN CRAWL SPACE UNDER FIRST
 FLOOR SHALL NOT BE INSTALLED IN OR
 WITHIN 4 INCHES OF THE GROUND AS PER
 1997 SMC 605.4.
  
 3.PLEASE SPECIFY MATERIAL AND R-VALUE
 OF ALL DUCTWORK BEING INSTALLED.
  
 4.INDICATE SIZE LOCATION OF LIQUID AND
 SUCTION REFRIGERANT LINES.
  
 5.INDICATE LOCATION OF CONDENSER
 UNITS.PLAN SHEET A000 SHOWS COND.
 UNITS IN EXCESS OF 30' FROM THE
 HOUSE.PLEASE REFER TO MANUFACTURER
 INSTALLATION INSTRUCTIONS FOR LINE
 SIZE FOR THIS DISTANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.