Plan Review Notes
Plan Review Notes For Permit 01101224
Permit Number 01101224
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-05 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PANELS ARE SHOWN AT 22,000, WHAT ABOUT
 MAIN? IS THE 22,000 FOR BREAKERS IN
 PANELS ALSO?
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 NOTE; MISSING IN BEDROOM #3 ALSO, SD
 SHOWN NEAR KITCHEN DOOR NEEDS TO BE A
 MIN OF 3` NFPA-72 2-5.2.1.6
  
 5)NOTE: PLEASE NOTE THE MISSING SMALL
 APPLIANCE CIRCUITS ON PANEL SCHEDULES.
 210-11-C-1
  
 6)NOTE: PLEASE NOTE THAT ONLY ONE PANEL
 IS SHOWN ON PLANS? RISER SHOWS TWO?
  
 7)PLEASE NOTE THAT THE ELECTRICAL PANEL
 IS SHOWN IN BATHROOM. THIS IS NOT
 PERMITTED PER 240-24E. PLEASE NOTE THAT
 PANEL CLEARENCE PER 110-26
  
 8)NOTE:PLEASE NOTE THAT PANEL SCHEDULES
 DO NOT CORRELATE>>> "A" SHOWS 3-AHU`S
 AND "B" SHOWS CU`S 1,2A,2B AND 3???
 PLEASE CLARIFY.
  
 9)NOTE: PLEASE SHOW ALL AHU`S AND CU`S
 ON PLANS AND DISCONNECTS PER 440-11 AND
 RECEPTS FOR SERVICE.
  
 10)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN MAIN AND
 PANEL "A". 250-122
  
 11)NOTE: PLEASE CLARIFY WHERE PANEL "B"
 IS BEING FED FROM? PANEL SCHEDULE "A"
 DOES NOT HAVE PANEL "B" ON SCHED.
  
 12)NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 GREAT ROOM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372