Plan Review Notes
Plan Review Notes For Permit 01101224
Permit Number 01101224
Review Stop B
Sequence Number 1
Notes
Date Text
2001-11-19 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01101224
 421 31ST STREET
 CONT: MARION CONST.
 TEL: 659-5192
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET A100: EXTERIOR DOOR OPENINGS
 VS. LANDINGS SEE SBC 1012.1.6.
 B) FACTORY BAR-B-Q: SBC 2808 SHALL
 REQUIRE THE MANUFACTURES SPEC.(2 COPIES)
 C) EXTERIOR FIREPLACE, ADDITIONAL
 INFORMATIOIN REQUIRED, FACTORY BUILT OR
 MASONARY?
 D) GREAT ROOM: 125 MB TUH, FIREPLACE,
 ADDITIONAL INFORMATION REQUIRED, FACTORY
 BUILT IF SO MUST COMPLY WITH UL 127 PRO-
 VIDE MANUFACTURES SPEC. IF MASONARY PROV
 IDE INFORMATION ON FIRE BOX SIZE &
 CHIMNEY FLUE SIZE, MISSING CHIMNEY ON
 ELEVATION, SHOW COMPLIANCE WITH SBC2804.
 2.4, SEE CHIMNEY HEIGTH REQUIREMENTS.
 E) FIREPLACES FRESH AIR INTAKE REQUIREME
 NTS, & FIREPLACE DOORS REQUIREMENTS SEE
 ENERGY CODE.
  
 2)- SHEET 301:
 A) STEM WALL TO LOW SEE 2304.2.5*
 STUCCO STOP REQUIREMENTS 6" CLEARENCE
 BETWEEN STUCCO, SHEETHING AND GROUND.
 B) DETAIL "C" PORTE COCHERE
 1) WALL SECTION VS (2X6 POST/ 4)?
 SBC 2308.1.5 REQUIRES TOP/ BOTTOM
 PLATES?
 2) WHAT TYPE OF ANCHOR IS TO BE USED
 IN STEM WALL CONSTRUCTION?
 3) WHAT LENGTH OF MICROLAM IS TO BE
 USED? HOW MANY SUPPORTS?
  
 3)- MISSINGROOF FRAMING PLAN, A101
 HOLDOWN SCHEDULE DOESN'T INDICATETHE
 LOCATIONS OF THESE ANCHORS OR THE MAGNIT
 UDE OF FORCES TO BE RESISTED?
  
 4)- A101 NEW BEDROOM # 3 WINDOWS DO NOT
 MEET THE EGRESS REQUIREMENTS OF 5.7 SQ.
 FT. OPEN AREA. SBC 1005.4.4. ARE THE
 WINDOWS IN THE OTHER SLEEPING ROOMS
 BEING REPLACED? IF SO THEY ALSO WILL
 NEED TO COMPLY!
  
 5)- BATH #2 WINDOW AND SHOWER DOOR,
 HAZARDOUS LOCATION SBC 2405.2.1.
  
 6)- MISSING PRODUCT APPROVAL REPORT FOR
 ROOFING ASSEMBLIES, TESTED FOR 110 MPH.
 PROVIDE 2 COPIES SBCCI OR DADE COUNTY
 REPORTS ARE ACCEPTABLE.
  
 7)- PLANS WILL BE REQUIRED TO HAVE
 PALM BEACH COUNTY IMPACT FEES STAMP
 BEFORE PERMIT ISSUANCE.
  
 8)- SHOW COMPLIANCE WITH OPENING VENTI-
 LATION AS IN 1804.6.2.1.(3) TAKE REDUCTI
 ON FOR VAPOR BARRIER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412