Plan Review Notes
Plan Review Notes For Permit 01101223
Permit Number 01101223
Review Stop E
Sequence Number 3
Notes
Date Text
2002-03-22 00:00:00************** PROVISO/REVISION ********
  
 THE FOLLOWING NEEDS TO BE REVISED ON
 PLANS BEFORE ANY FINAL ELECTRICAL
 INSPECTION IS CALLED IN.
 HAVE PLANS SUBMITTED FOR REVISION AND
 REVIEW. PAY REVISON FEE.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 4)NOTE: PLEASE SHOW LOCATION OF SERVICE
  
 5)NOTE: PLEASE NOTE, DISCONNECT FOR
 A/C COND UNIT NEEDS TO BE SHOWN PER
 440-11.
  
 PLEASE SUBMIT ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 ETX 8372