2002-03-22 00:00:00 | ************** PROVISO/REVISION ******** | | | | THE FOLLOWING NEEDS TO BE REVISED ON | | PLANS BEFORE ANY FINAL ELECTRICAL | | INSPECTION IS CALLED IN. | | HAVE PLANS SUBMITTED FOR REVISION AND | | REVIEW. PAY REVISON FEE. | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3) PLEASE CLARIFY EQUIPMENT GROUNDING | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | AND PANEL(S). EQUIPMENT GROUNDING | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | 4)NOTE: PLEASE SHOW LOCATION OF SERVICE | | | | 5)NOTE: PLEASE NOTE, DISCONNECT FOR | | A/C COND UNIT NEEDS TO BE SHOWN PER | | 440-11. | | | | PLEASE SUBMIT ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 ETX 8372 |
|