2001-10-23 00:00:00 | ******************* UNSAT ************ |
| |
| 1)NOTE: PLEASE NOTE THAT NO DIAGRAM |
| WAS SUBMITTED FOR NEW SERVICE?? 215-5 |
| SIZES.WIRE,CONDUITS,GROUNDING ETC. |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210-8-A-6. |
| |
| 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 6)NOTE: PLEASE SUBMIT PLANS THAT ARE |
| MORE CLEAR. PER 104.2.1 AND 104.2.7 |
| CLARITY OF PLANS |
| |
| 7)NOTE: PLEASE NOTE THAT IF THERE IS |
| GOING TO BE ANY LV TV,OR PHONE, PLEASE |
| SHOW ON PLANS. OTHERWISE SEPARTE PLANS |
| WILL HAVE TO BE SUBMITTED AT A LATER |
| DATE. |
| |
| 8))PLEASE NOTE EITHER MISSING EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210-70 OF THE NEC. |
| PLEASE NOTE MISSING LIGHTING IN SOME |
| LOCATIONS, SHOWN AS "JB" KITCHEN/PORCH/ |
| LAUNDRY RM/ BATH? ETC/ |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |