Plan Review Notes
Plan Review Notes For Permit 01101223
Permit Number 01101223
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-23 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT NO DIAGRAM
 WAS SUBMITTED FOR NEW SERVICE?? 215-5
 SIZES.WIRE,CONDUITS,GROUNDING ETC.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6)NOTE: PLEASE SUBMIT PLANS THAT ARE
 MORE CLEAR. PER 104.2.1 AND 104.2.7
 CLARITY OF PLANS
  
 7)NOTE: PLEASE NOTE THAT IF THERE IS
 GOING TO BE ANY LV TV,OR PHONE, PLEASE
 SHOW ON PLANS. OTHERWISE SEPARTE PLANS
 WILL HAVE TO BE SUBMITTED AT A LATER
 DATE.
  
 8))PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE MISSING LIGHTING IN SOME
 LOCATIONS, SHOWN AS "JB" KITCHEN/PORCH/
 LAUNDRY RM/ BATH? ETC/
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372