2001-11-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101223
 647 57TH STREET
 CONT: RITEWAY INSURANCE REPAIR
 CGC-048689
 TEL: (954) 923-3677
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- FL. S.S. 489.113(3B)/(3G) STATE
 CONTRACTOR CAN NOT INSTALL ROOF SHINGLES
 ON A REMODEL, ONLY ON NEW ROOF.
  
 2)- MISSING ROOFING PRODUCT APPROVAL
 FOR ROOFING SYSTEM. SBCCI OR DADE COUNTY
 PRODUCT APPROVAL REQUIRED UNDER SEPERATE
 PERMIT WITH ASSOCIATED FEES.
  
 3)- SBC 1606.2.6.2COMPONENTS & CLADDING
 (2) COPIES OF PRODUCT APPROVALS WILL BE
 REQUIRED FOR ALL EXTERIOR OPENINGS,
 EITHER SBCCI OR DADE COUNTY PRODUCT
 APPROVAL REQUIRED;
 WINDOWS
 SWING DOORS
 GARAGE DOORS OVERHEAD OR ROLL UP
 SKYLIGHTS
 STORM SHUTTERS.
  
 3)- SBC 1005.4.1:EVERY SLEEPING ROOM
 ON THE FIRST FLOOR WILL REQUIRE EMERGEN-
 CY ESCAPE AND RESCUE OPENINGS, STATE
 SIZE.
  
 4)- SBC 1707.4: GLAZED OPENINNGS REQUIRE
 1.5 TIMES THE DESIGN PRESSURE, TEST
 REPORT FOR WIND, SEE ATTACHMENT.
  
 5)- SBC 1606.4.1*/ 1707.4.1* GLAZED
 OPENINGS WILL REQUIRE EITHER IMPACT
 RESISTANT GLAZING OR STORM SHUTTERS
 PASSING THE LARGE MISSLE IMPACT TESTING
 REQUIREMENTS, WITH CITY REQUIREMENTS
 KEY PLAACEMENT PLAN & INSTALLATION SCHED
 ULE, SEE ATTACHMENT.
  
 6)- SBC 1606.2.6.1 MAIN WIND FORCE RESIS
 TING SYSTEM. INDICATE WHAT TYPE OF
 FASTENERS ARE TO BE USED TO RESIST VERTI
 CAL AND HORIZONTAL WIND LOADS AND INDICA
 TE THE LOADS THAT EACH TYPE OF MECHANISM
 SHALL BE CAPABLE OF RESISTING.
  
 7)- CITY CODE 7.2 PERMIT FEES SHALL BE
 CALCULAETED USING THE STANDARD BUILDING
 CODE EVALUATION TABLES LATEST EDITION.
 832 SQ FT= $65345.00X .60 ( REMODEL)=
 $ 39,207.00 ADDITIONAL FEES DUE.