Plan Review Notes For Permit 01101180 |
Permit Number |
01101180 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-30 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PLEASE PROVIDE MINIMUM FIXTURE CALCU- | | LATIONS. SHOW GROSS SQUARE FOOTAGE AND | | NET SQUARE FOOTAGE. SHOW USAGE OF BLDG. | | 2) PAGE A5.1 DETAILS 2 & 3, REMOVABLE | | PIPE GUARD NOT APPROVED FOR BREAK ROOM | | SINK. SINK SHALL COMPLY WITH FACBC SEC | | 4.24.3 27" HIGH/30"WIDE/ & 19" DEEP. | | 3) PAGE PO.1 DOMESTIC WATER ISOMETRIC, | | WATER HAMMER ARRESTORS SHALL BE PLACED | | NEAR FIXTURES NOT ON TOP OF DROP AS | | SHOWN. | | 4) PAGE PO.1 PLUMBING NOTES #13, AIR | | CHAMBERS ARE QUICK FIX AND IF USED SHALL | | COMPLY WITH SPC SEC 607.8.3 AND BE | | ACCESSIBLE AND RECHARGEABLE PER WH-PDI | | 201. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|