2001-10-30 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLEASE PROVIDE MINIMUM FIXTURE CALCU-
 LATIONS. SHOW GROSS SQUARE FOOTAGE AND
 NET SQUARE FOOTAGE. SHOW USAGE OF BLDG.
 2) PAGE A5.1 DETAILS 2 & 3, REMOVABLE
 PIPE GUARD NOT APPROVED FOR BREAK ROOM
 SINK. SINK SHALL COMPLY WITH FACBC SEC
 4.24.3 27" HIGH/30"WIDE/ & 19" DEEP.
 3) PAGE PO.1 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTORS SHALL BE PLACED
 NEAR FIXTURES NOT ON TOP OF DROP AS
 SHOWN.
 4) PAGE PO.1 PLUMBING NOTES #13, AIR
 CHAMBERS ARE QUICK FIX AND IF USED SHALL
 COMPLY WITH SPC SEC 607.8.3 AND BE
 ACCESSIBLE AND RECHARGEABLE PER WH-PDI
 201.
  