Plan Review Notes For Permit 01100853
Permit Number 01100853
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-15 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.PROVIDE ENGERGY CALCULATIONS AS
 PER 1997 FLORIDA ENERGY CODE SECTION
 101.4.1.1, SHOW COMPLIANCE WITH
 CHAPTER 6 METHOD C.
  
 2.COOLING AND HEATING DESIGN LOADS,
 FOR THE PURPOSE OF SIZING HVAC
 SYSTEMS, SHALL BE DETERMINED FOR
 EACH ZONE WITHIN A DWELLING IN
 ACCORDANCE WITH ACCA MANUAL J, ACCA
 MANUAL N OR THE ASHRAE COOLING AND
 HEATING LOAD CALCULATION MANUAL
 SECOND EDITION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.