Plan Review Notes
Plan Review Notes For Permit 01100845
Permit Number 01100845
Review Stop R
Sequence Number 1
Notes
Date Text
2001-11-20 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE IMPORTANCE FACTOR LISTED ON C-1
 IS INCORRECT, IT SHOULD BE 1.0 FOR 97
 SBC 1606.
  
 3) THE FOOTING DIMENSIONS FOR SECTIONS A
 & B ON A-5 ARE INCORRECT. THE F-1 FOOT-
 INGS ARE INDICATED AS 16" DEEP ON S-1.
  
 4) THE PLANS INDICATE R-30 CEILING
 INSULATION AND THE ENERGY CALCULATIONS
 LIST R- 19. PLEASE CLARIFY.
  
 5) SEMCO AND HUGHES HAVE BEEN PURCHASED
 BY USP. SOME OF THEIR CONNECTORS HAVE
 VALUES THAT ARE CHANGED AND SOME ARE NO
 LONGER AVAILABLE. PLEASE PROVIDE A
 REVISED TRUSS ANCHOR SCHEDULE. CONSULT
 USP TECHNICAL ASSISTANCE FOR REDUCED
 LOAD VALUES FOR INSTALLATIONS OF EMBEDD-
 ED TRUSS ANCHORS SPACED CLOSER THAN 8"
 AND WHEN USING LESS THAN THE SPECIFIED
 NUMBER OF FASTENERS.
  
 6) THERE IS NO TRUSS ANCHOR SPECIFIED
 FOR ONE END OF THE GIRDER AT THE GARAGE.
  
 7) NOTE THREE ON S-3 INCORRECTLY
 REFERENCES ASCE 7-93. THE DESIGN MUST BE
 BASED ON 97 SBC SECTION 1606 FOR 110 MPH
 OR ASCE 7-95 FOR 140 MPH. PLEASE CORRECT
  
 8) THE ROOF PLYWOOD SHEATHING NAILING
 SCHEDULE ON THE TOP OF S-2 LISTS ZONES
 RI AND SI. THE SPECIAL NAILING ZONES IN
 THE CITY OF WPB AMENDMENTS TO THE 97 SBC
 ARE DESIGNATED AS ZONES 1,2 AND 3.
 PLEASE CORRECT.
  
 9) THE PRODUCT APPROVAL FOR THE GLASS
 BLOCK EXPIRED PRIOR TO APPLICATION FOR
 PERMIT.
  
 10) PROVIDE INFORMATION ON GLASS BLOCK
 THAT INDICATES THAT THE BLOCK USED AT
 THE SHOWER HAS A MINIMUM UNIFORM FACE
 THICKNESS OF 0.25 INCH, TO COMPLY WITH
 97 SBC 2405.2 GLASS IN HAZARDOUS
 LOCATIONS.
  
 11) PROVIDE PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS USED TO CONNECT
 THE SLIDING GLASS DOOR AND THE FIXED
 GLASS WINDOWS ABOVE.
  
 12) PROVIDE KEY PLAN, INSTALLATION
 SCHEDULE, METHOD OF INSTALLATION AND
 TYPE OF ANCHORS TO BE USED TO INSTALL
 STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202