2001-11-20 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE IMPORTANCE FACTOR LISTED ON C-1 |
| IS INCORRECT, IT SHOULD BE 1.0 FOR 97 |
| SBC 1606. |
| |
| 3) THE FOOTING DIMENSIONS FOR SECTIONS A |
| & B ON A-5 ARE INCORRECT. THE F-1 FOOT- |
| INGS ARE INDICATED AS 16" DEEP ON S-1. |
| |
| 4) THE PLANS INDICATE R-30 CEILING |
| INSULATION AND THE ENERGY CALCULATIONS |
| LIST R- 19. PLEASE CLARIFY. |
| |
| 5) SEMCO AND HUGHES HAVE BEEN PURCHASED |
| BY USP. SOME OF THEIR CONNECTORS HAVE |
| VALUES THAT ARE CHANGED AND SOME ARE NO |
| LONGER AVAILABLE. PLEASE PROVIDE A |
| REVISED TRUSS ANCHOR SCHEDULE. CONSULT |
| USP TECHNICAL ASSISTANCE FOR REDUCED |
| LOAD VALUES FOR INSTALLATIONS OF EMBEDD- |
| ED TRUSS ANCHORS SPACED CLOSER THAN 8" |
| AND WHEN USING LESS THAN THE SPECIFIED |
| NUMBER OF FASTENERS. |
| |
| 6) THERE IS NO TRUSS ANCHOR SPECIFIED |
| FOR ONE END OF THE GIRDER AT THE GARAGE. |
| |
| 7) NOTE THREE ON S-3 INCORRECTLY |
| REFERENCES ASCE 7-93. THE DESIGN MUST BE |
| BASED ON 97 SBC SECTION 1606 FOR 110 MPH |
| OR ASCE 7-95 FOR 140 MPH. PLEASE CORRECT |
| |
| 8) THE ROOF PLYWOOD SHEATHING NAILING |
| SCHEDULE ON THE TOP OF S-2 LISTS ZONES |
| RI AND SI. THE SPECIAL NAILING ZONES IN |
| THE CITY OF WPB AMENDMENTS TO THE 97 SBC |
| ARE DESIGNATED AS ZONES 1,2 AND 3. |
| PLEASE CORRECT. |
| |
| 9) THE PRODUCT APPROVAL FOR THE GLASS |
| BLOCK EXPIRED PRIOR TO APPLICATION FOR |
| PERMIT. |
| |
| 10) PROVIDE INFORMATION ON GLASS BLOCK |
| THAT INDICATES THAT THE BLOCK USED AT |
| THE SHOWER HAS A MINIMUM UNIFORM FACE |
| THICKNESS OF 0.25 INCH, TO COMPLY WITH |
| 97 SBC 2405.2 GLASS IN HAZARDOUS |
| LOCATIONS. |
| |
| 11) PROVIDE PRODUCT APPROVALS FOR |
| STRUCTURAL MULLIONS USED TO CONNECT |
| THE SLIDING GLASS DOOR AND THE FIXED |
| GLASS WINDOWS ABOVE. |
| |
| 12) PROVIDE KEY PLAN, INSTALLATION |
| SCHEDULE, METHOD OF INSTALLATION AND |
| TYPE OF ANCHORS TO BE USED TO INSTALL |
| STORM PANELS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |