Plan Review Notes For Permit 01100837 |
Permit Number |
01100837 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-06 00:00:00 | ************BUILDING PROVISO************ | | | | SBC 104.2.2 | | | | 1. SUBMIT CURRENT PRODUCT APPROVALS FOR | | THE FOLLOWING EXPIRED: | | A. S/H WINDOWS | | B. GLASS BLOCK | | | | 2. SHEET S-1 REFERENCES L-19 LINTEL | | SHOULD BE L-17 PER TABLE. | | 3. SHEET S-3 CONNECTOR SCHEDULE SHOWS | | "C" TO BE MAX.. 1210# UPLIFT. DRAWING | | SHOWS "C" AS NWU 1363#. | | 4. PLANS MUST BE TAKEN BACK TO PBC TO | | PAY ADD'L IMPACT FEES BECAUSE BLDG. | | PERMIT WAS APPLIED FOR AFTER 9/28/01 |
|