Plan Review Notes For Permit 01100577 |
Permit Number |
01100577 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-11-02 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE THAT WIRING DIAGRAM | | FOR SPA UNIT IS NOT ENOUGH. | | AS ASK FOR ON FIRST REVIEW, DEPENDING | | ON SIZE OF UNIT? | | PLEASE NOTE THAT UNIT IS SHOWN AS 50A OR | | 60A? WHICH ONE? PLEASE NOTE THAT NO | | LOAD CALCULATIONS WERE SUBMITTED? SIZE | | OF EXISTING SERVICE? | | PLEASE NOTE THAT PLANS STILL NEED TO | | SHOW WIRING TO UNIT,WIRE SIZE, CONDUIT, | | GROUNDING.. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|