2001-11-02 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT WIRING DIAGRAM
 FOR SPA UNIT IS NOT ENOUGH.
 AS ASK FOR ON FIRST REVIEW, DEPENDING
 ON SIZE OF UNIT?
 PLEASE NOTE THAT UNIT IS SHOWN AS 50A OR
 60A? WHICH ONE? PLEASE NOTE THAT NO
 LOAD CALCULATIONS WERE SUBMITTED? SIZE
 OF EXISTING SERVICE?
 PLEASE NOTE THAT PLANS STILL NEED TO
 SHOW WIRING TO UNIT,WIRE SIZE, CONDUIT,
 GROUNDING..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  