Plan Review Notes For Permit 01100537 |
Permit Number |
01100537 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-09 00:00:00 | 1) WHY IS THERE NO MANUAL PULL STATION | | SHOWN NEAR THE STAIRWAY. IS THERE AN | | EXISTING ONE? | | 2) NO HORN STROBES SHOWN IN THE AREA | | OF THE MEDITATION, SALON, WAITING, OR | | MEDITATION AREAS. | | 3) A SMOKE DETECTOR IS SHOWN IN THE | | LAUNDRY ROOM. A HEAT DETECTOR WOULD | | BETTER SERVE THIS LOCATION. | | 4) WHY IS THERE NO SMOKE DETECTOR | | SHOWN AT THE ELEVATOR AREA. IS THERE | | AN EXISTING ONE? | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|