2001-10-21 00:00:00PLUMBING PLAN REVIEW,DENIED
 (1) SHT A1,MINIMUM FACILITIES, TAB 407
 REQUIRES 3 W/C'S AND 3 LAVS, IN RM 210
 WOMENS REST RM.
 (2)SHT A-1-5, BREAK SINK, RM 219, COMPLY
 WITH FACBC-97 SEC 4.24, HGTH 34" AFF.
 (3)SHT P1 SPECIFICATIONS, LIST MATERIALS
 FOR DWV AND WATER PIPING, SEC 104.2
 END OF COMMENTSPAUL SCHMITZ