Plan Review Notes
Plan Review Notes For Permit 01100285
Permit Number 01100285
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-24 00:00:00******************* UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY OCP FOR "EXISTING
 "DS-2 FEEDING NEW '2M'. PLEASE NOTE
 PLANS DO NOT SHOW SIZE.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%. PLEASE NOTE THAT LOADS ARE SHOWN
 AT CONNECTED/AMPS/DEMAND? NEED TO SHOW
 WATTS/SQ FT/OUTLETS LOADS. ?= 180VA.
 PLEASE NOTE THAT LOAD SHOWN FOR OUTELTS
 IS AT 13.1KW, PLEASE NOTE BY ROUGH
 COUNT IT APPEARS TO BE HIGHER?
 PLEASE CLARIFY BY SHOWING.
 LARGEST MOTOR AT 125% ALSO.
 215-5. 215-2,230-42,,,,,
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372