Plan Review Notes
Plan Review Notes For Permit 01100130
Permit Number 01100130
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-24 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 MAIN DISCONNECTS AND PANELS.
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 3)NOTE: PLEASE NOTE SMOKE DETECTOR INTO
 BEDROOM. NFPA-72 2-2.1.1.1
  
 4)NOTE: PLEASE NOTE OUTLET IN BATH TO
 BE AJACENT TO SINK. 210-52 D
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  