Plan Review Notes For Permit 01100130 |
Permit Number |
01100130 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-24 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | MAIN DISCONNECTS AND PANELS. | | | | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | 3)NOTE: PLEASE NOTE SMOKE DETECTOR INTO | | BEDROOM. NFPA-72 2-2.1.1.1 | | | | 4)NOTE: PLEASE NOTE OUTLET IN BATH TO | | BE AJACENT TO SINK. 210-52 D | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|