2001-11-14 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01100130
 2320 TECUMSEH DR
 CONT: BILL FREE & ASSOC
 TEL: 624-0149
 CEL: 662-3652
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET A-7:TYPICAL WALL SECTION
 A) FOUNDATION NOTES 18"X18" CONC. MONO.
 FTG. A SECOND NOTE INDICATES 12"
 FROM FINISH FLOOR TO GRADE ALLOWING
 6" OF THE FOUNDATION TO BENEATH
 GRADE. SBC1804.1.3 A MINIMUM OF 12"
 OF THE FOUNDATION MUST BE BELOW
 GRADE.
 B) MISSING SBC 1814.3.3 MOISTURE BAR-
 RIER FOR MONOSLAB.
 C) TERMITE TREATMENT: SBC 1804.2/ 2304.
 1.2
  
 2)- MISSING INFORMATION, ON THE INTERIOR
 BEARING WALLS, MONOLITHIC FOOTERS, SUNK-
 ENED FLOOR AREAS. FOUNDATION SIZE, STEEL
 AND ANCHOR BOLTS.
  
 3)- MISSING INFORMATION ON CONCRETE
 COLUMNS ASWELL AS MASONRY REINFORCEMENT.
 COLUMN SIZE,STEEL HOOPS.
  
 4)- MISSING INFORMATION FOR TIE BEAM OR
 BOND BEAM CONSTRUCTION, SIZE,DEPTH,
 STIRRUPS STEEL?
  
 5)- MISSING TRUSS PLAN WITH THE MAGNI-
 TUDE OF LOADS TO BE RESISTED, TYPE OF
 HURRICANE STRAPS &TIES ANSD ALLOWABLE
 LOADS.
  
 6)- SHEET A-4, ADDITIONAL INFORMATION
 ON THE FRAMING & ATTACHMENT OF CHIMNEY,
 DETAIL OF 2 FLUES, PLANS INDICATE 1
 FLUE? 2 FIREPLACES?
  
 7)- ENERGY SHEETS DO NOT INDICATE THE
 USE OF A FIREPLACE?
  
 8)-FACTORY PREBUILT FIREPLACES/ CHIMNEYS
 SHALL COMPLY WITH UL 127, SUBMIT SPECIFI
 CATIONS.
  
 9)- SBC 2810 FRESH AIR INTAKES ARE RE-
 QUIRED ON THE FIREPLACE.
  
 10)- SBC 2809 GAS LOGS SHALL BE INSTALL-
 ED IN ACCORDANCE WITH REGULATIONS OF THE
 STANDARD GAS CODE.
  
 11)- SHEET A-4 FRONT ELEVATION, ADDTION-
 AL INFORMATION REQUIREDON THE CONSTRUCTI
 ON OF THE FRONT ENTRY.
  
 12)- A-7 METAL LATH SOFFIT: HIRIB ATTACH
 MENT ASPER 2504.2.2 SEE ASTM C 1063.
 7.10.2.3 HORIZONTAL FRAMING MEMBERS
 SHALL HAVE NAILS OR STAPLES TO PROVIDE
 AT LEAST 1 3/4" PENETRATION INTO HORIZON
 TAL FRAMING MEMBERS.
  
 13)- SHEET A-8 JAMB/ HEAD DOOR DETAIL,
 MISPRINT, 1/2" X 3" CONCRETE SCREWS.
  
 14)- INDICATE THE POSITIVE/ NEGATIVE
 PRESSURES ASSOCIATED WITH WINDOW & DOOR
 OPENINGS, INDICATE ON ELEVATIONS, END
 ZONES & INTERIOR ZONES.
  
 15)- SBC 1606.2.6.2COMPONENTS & CLADDING
 MISSING OR EXPIRED PRODUCT REPORTS (2)
 COPIES REQUIRED.
 A) WINDOWS- 4000 ALUM SERIES SINGLE
 HUNG - EXPIRED
 B) DOORS- FRENCH DOORS NO REPORT
 C) STORM SHUTTERS- MISSING, KEY PLAN
 INDICATING LOCATION OF SHUTTERS &
 FASTENING SCHEDULE, SAMPLE ATTACHED
  
 PLANS ARE OF A CONCEPTUAL DESIGN IN NA-
 TURE, A THOROUGH REVIEW CAN'T BE COM-
 PLETED AT THIS TIME.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412