2001-11-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT# 01100130 |
| 2320 TECUMSEH DR |
| CONT: BILL FREE & ASSOC |
| TEL: 624-0149 |
| CEL: 662-3652 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| |
| 1)- SHEET A-7:TYPICAL WALL SECTION |
| A) FOUNDATION NOTES 18"X18" CONC. MONO. |
| FTG. A SECOND NOTE INDICATES 12" |
| FROM FINISH FLOOR TO GRADE ALLOWING |
| 6" OF THE FOUNDATION TO BENEATH |
| GRADE. SBC1804.1.3 A MINIMUM OF 12" |
| OF THE FOUNDATION MUST BE BELOW |
| GRADE. |
| B) MISSING SBC 1814.3.3 MOISTURE BAR- |
| RIER FOR MONOSLAB. |
| C) TERMITE TREATMENT: SBC 1804.2/ 2304. |
| 1.2 |
| |
| 2)- MISSING INFORMATION, ON THE INTERIOR |
| BEARING WALLS, MONOLITHIC FOOTERS, SUNK- |
| ENED FLOOR AREAS. FOUNDATION SIZE, STEEL |
| AND ANCHOR BOLTS. |
| |
| 3)- MISSING INFORMATION ON CONCRETE |
| COLUMNS ASWELL AS MASONRY REINFORCEMENT. |
| COLUMN SIZE,STEEL HOOPS. |
| |
| 4)- MISSING INFORMATION FOR TIE BEAM OR |
| BOND BEAM CONSTRUCTION, SIZE,DEPTH, |
| STIRRUPS STEEL? |
| |
| 5)- MISSING TRUSS PLAN WITH THE MAGNI- |
| TUDE OF LOADS TO BE RESISTED, TYPE OF |
| HURRICANE STRAPS &TIES ANSD ALLOWABLE |
| LOADS. |
| |
| 6)- SHEET A-4, ADDITIONAL INFORMATION |
| ON THE FRAMING & ATTACHMENT OF CHIMNEY, |
| DETAIL OF 2 FLUES, PLANS INDICATE 1 |
| FLUE? 2 FIREPLACES? |
| |
| 7)- ENERGY SHEETS DO NOT INDICATE THE |
| USE OF A FIREPLACE? |
| |
| 8)-FACTORY PREBUILT FIREPLACES/ CHIMNEYS |
| SHALL COMPLY WITH UL 127, SUBMIT SPECIFI |
| CATIONS. |
| |
| 9)- SBC 2810 FRESH AIR INTAKES ARE RE- |
| QUIRED ON THE FIREPLACE. |
| |
| 10)- SBC 2809 GAS LOGS SHALL BE INSTALL- |
| ED IN ACCORDANCE WITH REGULATIONS OF THE |
| STANDARD GAS CODE. |
| |
| 11)- SHEET A-4 FRONT ELEVATION, ADDTION- |
| AL INFORMATION REQUIREDON THE CONSTRUCTI |
| ON OF THE FRONT ENTRY. |
| |
| 12)- A-7 METAL LATH SOFFIT: HIRIB ATTACH |
| MENT ASPER 2504.2.2 SEE ASTM C 1063. |
| 7.10.2.3 HORIZONTAL FRAMING MEMBERS |
| SHALL HAVE NAILS OR STAPLES TO PROVIDE |
| AT LEAST 1 3/4" PENETRATION INTO HORIZON |
| TAL FRAMING MEMBERS. |
| |
| 13)- SHEET A-8 JAMB/ HEAD DOOR DETAIL, |
| MISPRINT, 1/2" X 3" CONCRETE SCREWS. |
| |
| 14)- INDICATE THE POSITIVE/ NEGATIVE |
| PRESSURES ASSOCIATED WITH WINDOW & DOOR |
| OPENINGS, INDICATE ON ELEVATIONS, END |
| ZONES & INTERIOR ZONES. |
| |
| 15)- SBC 1606.2.6.2COMPONENTS & CLADDING |
| MISSING OR EXPIRED PRODUCT REPORTS (2) |
| COPIES REQUIRED. |
| A) WINDOWS- 4000 ALUM SERIES SINGLE |
| HUNG - EXPIRED |
| B) DOORS- FRENCH DOORS NO REPORT |
| C) STORM SHUTTERS- MISSING, KEY PLAN |
| INDICATING LOCATION OF SHUTTERS & |
| FASTENING SCHEDULE, SAMPLE ATTACHED |
| |
| PLANS ARE OF A CONCEPTUAL DESIGN IN NA- |
| TURE, A THOROUGH REVIEW CAN'T BE COM- |
| PLETED AT THIS TIME. |
| |
| BUILDING PLAN REVIEW |