Plan Review Notes
Plan Review Notes For Permit 01091718
Permit Number 01091718
Review Stop R
Sequence Number 1
Notes
Date Text
2001-11-14 00:00:00*************BUILDING UNSAT*************
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE DOCUMENTATION THAT THERE IS
 AN EGRESS EASEMENT THAT WILL PROVIDE AN
 UNOBSTRUCTED PATH OF TRAVEL FROM THE
 ACCESS DOOR THROUGH THE ADJOINING LOT TO
 A PUBLIC AREA. PROVISIONS THAT WILL
 PREVENT THE OWNER OF THE ADJACENT
 PROPERTY FROM BLOCKING THE ACCESS DOOR
 WITH FENCES, SHRUBBERY OR OTHER IS
 REQUIRED. THE SITUATION OF THE ACCESS
 DOOR PROVIDING DIRECT ACCESS TO A POOL
 MUST BE ADDRESSED SHOULD THE OWNER OF
 THE ADJACENT PROPERTY EVER WANT TO
 INSTALL A PRIVATE POOL ON HIS PROPERTY
 MUST ALSO BE ADDRESSED.
  
 3) PROVIDE ACCESS TO ATTIC PER 97 SBC
 SEC. 2309.6, IF THE CLEAR HEIGHT OF THE
 ATTIC IS 24" OR MORE AT THE PEAK.
  
 4) THE EXTERIOR WALL SECTION,C ON SHEET
 A-3.0 INDICATES THE BOTTOM OF THE FOOTER
 AT 12" BELOW FINAL GRADE. THE SOIL
 REPORT REQUIRES THE FOUNDATION TO BEAR
 14" BELOW FINAL GRADE. PLEASE CORRECT.
  
 5) THE MASONRY OPENING FOR THE GLASS
 BLOCK AT THE KITCHEN IS INCORRECTLY
 LISTED AS 85 SQ.FT. THE M.O. FOR THE
 G.B. IN THE GREAT ROOM IS LISTED AS 42"
 X 26", WHICH WOULD BE FOR THREE COURSES
 OF FIVE BLOCKS, HOWEVER, THE PLANS
 INDICATE THREE COURSES OF FOUR BLOCKS.
 PLEASE CORRECT.
  
 6) THE PRODUCT APPROVALS SUBMITTED FOR
 STORM PANELS ARE INCOMPLETE. ONLY THE
 APPROVED DRAWINGS WERE SUBMITTED WITH
 THE KEY PLAN AND INSTALLATION SCHEDULE.
  
 7) PROVIDE THE MANUFACTURER'S SPECS. FOR
 THE 1 HOUR RATED GLASS BLOCK.
  
  
 TRUSSES
 UNSAT
  
 NOTE: SEMCO & HUGHES HAVE BEEN PURCHASED
 BY USP. SOME OF THE CONNECTOR CAPACITIES
 HAVE BEEN REDUCED AND OTHERS HAVE BEEN
 CONTINUED. PLEASE REFER TO THE LATEST
 USP CATALOG FOR TRUSS CONNECTOR
 INFORMATION.
  
 1) THE UPLIFT VALUES PROVIDED IN THE
 TRUSS ANCHOR SCHEDULE DO NOT AGREE WITH
 THE VALUES LISTED IN THE CATALOG. PLEASE
 THE CRITERIA USED TO DETERMINE THE
 UPLIFT VALUES FOR THE CONNECTORS WHEN
 NUMBER OF FASTENERS DIFFERS FROM THOSE
 SPECIFIED BY THE MANUFACTURER.
  
 2) NO ANCHORS ARE SPECIFIED FOR JOINT 4
 OF TRUSSES T1.
  
 3) THE TRUSS DESIGN CERTIFICATION COVER
 SHEET DESIGNATES WINDLOADS IN COMPLIANCE
 WITH ASCE 7-95 FOR 150 MPH. SOME OF THE
 TRUSS DRAWINGS INDICATE 110 MPH WINDLOAD
 AND OTHERS 150 MPH. THE STRUCTURE IS
 DESIGNED TO ASCE 7-95 AND 145 MPH. PER
 SHEET S1. PLEASE CORRECT.
  
 4) THE TRUSS DRAWINGS INDICATE AN UPLIFT
 OF 1637# AT JOINT 9 FOR TRUSS T2. THIS
 EXCEEDS THE VALUE OF THE TA-15 CONNECTOR
 SPECIFIED. THE UPLIFT AT JOINT 1 IS
 2924# WHICH EXCEEDS THE CAPACITY OF THE
 TA-14 CONNECTOR SPECIFIED.
 UPLIFT VALUES IN YOUR SCHEDULE EXCEED
 THOSE LISTED IN CATALOG.
  
 5) TRUSS GT3; UPLIFT AT JOINT 1 (2725#)
 EXCEEDS THE TA-14 ANCHOR (1450#) AND AT
 JOINT 9 ( 2271#) EXCEEDS THE TA-15
 (1450#).
  
 6) TRUSS GT7; UPLIFT AT JOINT 24 (3699#)
 AND JOINT 13 (3245#) ARE QUESTIONABLE
 DUE TO THE CATALOG VALUES OF THE
 SPECIFIED ANCHORS AND THE REDUCTIONS IN
 CAPACITY DUE TO BEING LOCATED WITHIN
 8 INCHES OF EACH OTHER. THE SAME
 COMMENTS ARE APPLICABLE TO TRUSS GT7A.
  
 7) TRUSS GT11; UPLIFT AT JOINT 1 EXCEEDS
 SPECIFIED ANCHOR. THERE IS NO REDUCTION
 GIVEN FOR THE (3) ANCHORS LOCATED WITHIN
 8 INCHES OF EACH OTHER. SEE CATALOG.
  
 8) THE TURRET FRAMING PLAN INDICATES A
 TA-6 ANCHOR. THIS MARK IS NOT LISTED IN
 YOUR TRUSS ANCHOR SCHEDULE.
  
 9) PLEASE CLARIFY THE ANCHOR FOR TRUSS
 TT1 AT TURRET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202